2 sunny mini central 6000, 1 data pv generator connection, 2 data grid connection – SMA SMC 5000 Installation User Manual
Page 38: Sunny mini central 6000, Data pv generator connection, Data grid connection

Technical Documentation
SMA
Technologie AG
Page 38
SMC50_60-11:SE2006
Installation Guide
7.2 Sunny Mini Central 6000
7.2.1 Data PV Generator Connection
7.2.2 Data Grid Connection
Max. input open-circuit voltage
U
PV
0
600 V (at -10 °C module temperature)
Input voltage, MPP operation
U
PV
250 V ... 600 V DC
(250 V DC at 230 V AC)
Max. input current
I
PV max
26 A
Max. input power
P
PV
6300 W
Recommended generator
power
7000 Wp
All-pole disconnector on DC input side
DC plug connector
Surge voltage protection
thermally monitored varistors
Voltage ripple
U
PP
< 10 % of input voltage
Personnel protection
Ground Fault monitoring
(Riso > 2 MΩ)
Internal consumption in operation
< 7 W (stand-by)
Pole confusion prevention
by short-circuit diode
Nominal output power
P
ACnom
5500 W
Permanent output power at 45 °C
6000 W
Peak output power
P
ACmax
6000 W
Nominal output current
I
ACnom
24 A
Harmonic distortion of output
(with KUnom < 2 %, PAC > 0,5 PACnom)
T
HDIAC
4 %
Short-circuit resistance
Imax = 30 A
Operating range, grid voltage
U
AC
198 ... 260 V AC
(adjustable 180 ... 265 V)
Operating range, grid frequency
f
AC
49.8 ... 50.2 Hz
(adjustable 45.5 ... 54.5 Hz)
All-pole disconnector on grid side
independent disconnection device (MSD),
(2 independant systems)
Phase difference (related to basic wave of
current)
cos Phi
1
Overvoltage category
III
Test voltage
2 kV (1 s unit / 60 s type test)
Surge voltage test
4 kV (1.2/50 µs)
(serial interface: 6 kV)
Internal consumption in stand-by
0.25 W