beautypg.com

5 operation (operation), Operation (operation) – SMA SI 3324 User Manual

Page 54

background image

Parameter Lists

SMA

Technologie AG

Page 54

SI3324/4248-14:FE2406

User Manual

10.5 Operation (Operation)

Only change parameters marked with (Stby), when the Sunny Island 3324/
4248 is in standby mode. Appropriately set operational data can take effect
as soon as the "Enter" key is pressed. Incorrect values in these parameters can
probably not be corrected quickly enough to avoid potential damage to your
system.

All parameters marked with a (B) can be set while the system is running.

All parameters can be set using a connected PC/laptop with the Sunny Data
Control software, a Sunny WebBox or a Sunny Boy Control.

No.

Name

Range/
unit

Default

Description

40-1

BatChargeMode
(B)

Auto
Boost
Full
Equalize

Auto

Direct triggering of a battery charging
process.
Auto: The inverter automatically triggers
the different battery charging processes.
The selection of any other mode causes
the inverter to start the selected charging
process. Automatic operation is then
resumed after this.

40-2

Autostart
(B)

Off
On

Off

Autostart allows the inverter to
automatically restart (e.g. after a fault). If
AutoStart is set to "Off ", then the inverter
must always be manually started.

This manual is related to the following products: