Parameter Lists

User Manual

SI3324/4248-14:FE2406

Page 51

10.3 Adjustable System Parameters

Inverter Settings

Battery Settings

Only change parameters marked with (Stby), when the Sunny Island 3324/
4248 is in standby mode. Appropriately set operational data can take effect
as soon as the "Enter" key is pressed. Incorrect values in these parameters can
probably not be corrected quickly enough to avoid potential damage to your
system.

All parameters marked with a (B) can be set while the system is running.

All parameters can be set using a connected PC/laptop with the Sunny Data
Control software, a Sunny WebBox or a Sunny Boy Control.

No.

Name

Range/
unit

Default

Description

22-1

VacNominal
(B)

200 to 253 VAC

230

Setting of the inverter nominal output
voltage

No.

Name

Range/
unit

Default

Description

23-1

VdcBatNominal
(see section 11.4)

SI4248
42 to 48 VDC

48

Nominal battery voltage

SI3324
20 to 24 VDC

24

23-2

BatType
(see section 11.4)

VRLA
FLA

VRLA

The type of battery used in the system.
VRLA = Gel/Absorbed Glass Mat
battery
FLA = battery with liquid electrolyte
These parameters must be set when first
commissioning the system. After this, the
value can only be changed after you
have set the "23-5 New Battery"
parameter to the value "Reset". The Sunny
Island 3324/4248 will then again run
through the INIT phase.

23-3

AmpHoursBat
(see section 11.4)

100 to 6000 Ah

100

Battery capacity. These parameters must
be set when first commissioning the
system. After this, the value can only be
changed after you have set the "23-5
New Battery" parameter to the value
"Reset". The Sunny Island 3324/4248 will
then again run through the INIT phase.

23-4

AmpdcBatMax
(B)

SI4248
0 to 100 ADC

10

Maximum battery charging current

SI3324
0 to 140 ADC

10