Technical Data
SMA Solar Technology AG
82
SC20_25_35-IEN094521
Installation Guide
Power Consumption
Sunny Central Control Interfaces
Standards
Protection rating and ambient conditions
Own consumption in operation (P
day
)
< 1000 W
Standby operating consumption (P
night
)
< approx. 70 W
External power supply / grid structure
230 V, 50 Hz / 60 Hz / TN-S, TT
External pre-fuse for internal power supply
B 16 A, 1 pole
Communication (NET Piggy-Back, optional)
Analog, ISDN, Ethernet
Analog Inputs
1 x PT 100, 2 x A
in
a)
a)
Terminal for an analog sensor provided by the customer in two-wire and four-wire version.
Overvoltage protection for analog inputs
Optional
Sunny String-Monitor connection (COM1)
RS485
PC interface (COM3)
RS232
Floating contact (external fault detector)
1
EMC
EN 61000-6-2, EN 61000-6-4
CE conformity
Yes
Protection rating as per EN 60529
IP 20
Permissible ambient temperatures
–20 °C ... +40 °C
Relative humidity, non-condensing
15 % ... 95 %
Maximum altitude above sea level
1000 m
Fresh air consumption
3300 m³/h