SMA Solar Technology AG

Troubleshooting

Installation Guide

SB11_12_17-IEN100132

37

The approximate position of the ground fault can be determined from the ratio of the measured
voltages between plus against ground potential and minus against ground potential.
Example:

The ground fault is between the second and third module in this case.

3. Repeat step 2 for each string.

The table illustrated below shows the various results and corresponding measures.

☑ The ground fault check is finished.

Result

Action

☑ You have found a ground fault.

• The installer of the PV generator must

remedy the ground fault in the affected
string before you may reconnect the string
to the Sunny Boy.

• Do not reconnect the faulty string.
• Close and commission the Sunny Boy as

described in section 7.2 "Closing the
Sunny Boy" (page 33).

☑ You have found no ground fault.

It is likely that one of the thermally monitored
varistors is defective.

• Check the varistors as described in section

9.1.2 "Checking the Function of the
Varistors" (page 38).