Electrical Connection

SMA Solar Technology AG

20

SB11_12_17-IEN100132

Installation Guide

7. Lead the pressure screw and/or cable gland and socket tube via the AC cable.

8. Insert the protective earth PE (green-yellow) in the

screw terminal with the earth sign on the socket
element and tighten the screw.

9. Insert the neutral conductor N (blue) in the screw

terminal 1 on the socket and tighten the screw.

10. Place phase L (brown or black) into screw terminal

2 on the socket insert and tighten the screw.

11. Terminal 3 on the socket element remains unused.

12. Make sure the wires are securely connected.

Size used

Procedure

PG13.5

• Push the sealing ring into

the fastening case.

• Lead the pressure screw

PG13.5 and the
fastening case including
the sealing ring via the
AC cable.

• Lead the threaded

sleeve via the AC cable.

PG16

• Lead the cable gland

PG16 via the AC cable.

• Lead the threaded

sleeve via the AC cable.

This manual is related to the following products: