beautypg.com

SMA GRID CONNECT BOX 12 User Manual

Page 33

background image

SMA Solar Technology AG

12  Technical Data

Operating Manual

GRID-BOX-12-3-20-BE-en-10

33

Auxiliary electric circuits

General Data

Fuse

10x38 cylinder fuse

Maximum permitted fuse rating

F333 to F336: 1 A

Terminals for connecting the control cables

Spring-cage terminal

Minimum conductor cross-section

0.75 mm²

Maximum conductor cross-section

2.5 mm²

Number of line conductors

3

Permitted grid configuration

TN-S, TN-C-S or TT

AC voltage range between L1 and N

172.5 V to 265 V

AC voltage range between L1 and L2

300 V to 433 V

Rated frequency

50 Hz

Frequency range

45 Hz to 65 Hz

Rated impulse withstand voltage

4 kV (2,000 m)

Width x height x depth (with base)

600 mm x 1,400 mm x 435 mm

(incl. 200 mm base)

Weight

103 kg

Maximum operating altitude above mean sea level

3,000 m

Inner subdivision

Form 1 (no subdivision)

Exterior design

closed type

Installation

only fixed interior installation permitted

Construction type

fixed components

Suitable for use by electrically qualified persons or unqualified

persons

Installation of the system and replacement of

equipment by electrically qualified persons only /

actuation of test buttons and read-off of information

by unqualified persons permitted

Measures for protection against electric shock

Basic protection afforded by insulation materials and

covers / fault protection by grounding conductors

and short-circuit protection devices / personal

protection by residual-current devices

Degree of protection of enclosure*

IP55

Degree of protection with enclosure door open*

IP20

Pollution degree at the mounting location**

3

Pollution degree in the enclosure (micro-environment)

2

Protection class***

1

Overvoltage category****

Overvoltage category 3