P95-3 Zero Clearance Direct Vent Gas Fireplace

11

VENTING

FPI Direct Vent System Flex Horizontal Terminations Only

These venting systems, in combination with the P95-3 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by
Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram from the "Exterior
Vent Termination Locations" section.

FPI Direct Vent Flex System Termination
Kit (Part # 946-615) includes all the parts
needed to install the P95-3 with a maximum
run of 4 feet.

1) 8" dia. fl exible liner (4 ft. length)
2) 5" dia. fl exible liner (4 ft. length)
3) spring spacers (4)
4) thimble

(2)

5) AstroCap XL termination cap (1)
6) screws

(12)

7) tube of Mill Pac (1)
8) plated

screws

(8)

9) screws #8 x 1-1/2" Drill Point,
Stainless

Steel

(4)

10) vinyl siding standoff

If longer runs are needed, the FPI Direct Vent
system (Flex) kit is (Part # 946-616) which
includes all the parts needed to install the
P95-3 with a maximum 10' run.

1) 8" dia. fl exible liner (10 ft. length)
2) 5" dia. fl exible liner (10 ft. length)
3) spring spacers (7)
4) thimble

(2)

5) AstroCap XL termination cap (1)
6) screws

(12)

7) tube of Mill Pac (1)
8) plated

screws

(8)

9) screws #8 x 1-1/2" Drill Point,
Stainless

Steel

(4)

10) vinyl siding standoff

INSTALLATION

Notes:

1) Liner sections should be continuous

without any joints or seams.

2) Only Flex pipe purchased from FPI may

be used for Flex installations.

3) Horizontal vent must be supported every

3 feet.