beautypg.com

Switching inputs ext (x41) – HEIDENHAIN NPD 281 v.3 User Manual

Page 38

background image

38

Switching Inputs EXT (X41)

Weg

5

t

t

t

v

t

v

Pin 15
(A1)

Time curve of a signal at pin 15 for trigger limit (A1) = 5 mm , t

d

22 ms

Zero crossover

The display value “zero” activates the corresponding output
(pin 14). Minimum signal duration is 180 ms.

Path

Output

Measured value < Lower sorting limit

Measured value > Upper
sorting limit

Path

Lower limit Upper limit

Switching point

Switching signals

As soon as the trigger points defined in parameters are
reached, the corresponding outputs (pins 15,16) are activated.
You can set up to two trigger points. The switching point
“zero” has a separate output (see “Zero crossover”).

Signals for sorting and tolerance checking

If the sorting limits defined in parameters are exceeded, the
corresponding outputs (pins 17, 18) are activated.

Signals

Operating parameters

Pin

Switching signals

P62, switching limit 1

15

P63, switching limit 2

16

Sorting signals

P18, lower sorting limit

17

P19, upper sorting limit

18

t

d

t

d

Path

This manual is related to the following products: