Grass Valley 2000NET v3.2.2 User Manual
Page 62

62
2000NET Instruction Manual
Service
5.
Check that the particular event has been enabled in the frame.
•
For all events, check that the STATUS switch (Switch 1) on the S2
DIP switch block of the 2000NET module is Enabled.
•
For Module Failure-Fixed events:
Check that the MODULE switch (Switch 7) on the S1 DIP switch
block of the 2000NET module is Enabled, and
Check that the
SLOT STATUS REPORTING
parameter on the slot’s
SLOT
CONFIG
page is Enabled.
•
For Power Supply Failure-Fixed events:
Check that the PS1, PS2, PS3, or PS4 switch (Switch 1, 2, 3, or 4) on
the S1 DIP switch block of the 2000NET module is Enabled, and
Check that the
POWER SUPPLY STATUS REPORTING
parameter on the
power supply’s
CONFIGURATION
page is Enabled.
•
For 2000NET module Failure-Fixed events, check that the
NET CARD
STATUS REPORTING
parameter on the 2000NET module’s
CONFIGURA-
TION
page is Enabled.
•
For Hardware Switch change events, check that the
HARDWARE
SWITCH REPORTING
parameter on the 2000NET module’s
CONFIGURA-
TION
page is Enabled.
•
For Frame Bus Failure-Fixed events:
Check that the FRAME BUS switch (Switch 6) on the S1 DIP switch
block of the 2000NET module is Enabled, and
Check that the
FRAME BUS STATUS REPORTING
parameter on the
frame’s
CONFIGURATION
page is Enabled.
•
For Front Cover Removed -Installed events, check that the
COVER
STATUS REPORTING
parameter on the frame’s
CONFIGURATION
page is
Enabled.
•
For Frame Bus Failure-Fixed events:
Check that the FRAME BUS switch (Switch 6) on the S1 DIP switch
block of the 2000NET module is Enabled, and
Check that the
FRAME BUS STATUS REPORTING
parameter on the
frame’s
CONFIGURATION
page is Enabled.
•
For Cooling Fan Failure-Fixed events:
Check that the FAN switch (Switch 4) on the S1 DIP switch block of
the 2000NET module is Enabled, and
Check that the
FAN STATUS REPORTING
parameter on the frame’s
CON-
FIGURATION
page is Enabled.
•
For Module Health Failure-Fixed events,
Check that the MODULE switch (Switch 5) on the S1 DIP switch