Service

5.

Check that the particular event has been enabled in the frame.

For all events, check that the STATUS switch (Switch 1) on the S2
DIP switch block of the 2000NET module is Enabled.

For Module Failure-Fixed events:

Check that the MODULE switch (Switch 7) on the S1 DIP switch
block of the 2000NET module is Enabled, and

Check that the

SLOT STATUS REPORTING

parameter on the slot’s

SLOT

CONFIG

page is Enabled.

For Power Supply Failure-Fixed events:

Check that the PS1, PS2, PS3, or PS4 switch (Switch 1, 2, 3, or 4) on
the S1 DIP switch block of the 2000NET module is Enabled, and

Check that the

POWER SUPPLY STATUS REPORTING

parameter on the

power supply’s

CONFIGURATION

page is Enabled.

For 2000NET module Failure-Fixed events, check that the

NET CARD

STATUS REPORTING

parameter on the 2000NET module’s

CONFIGURA-

TION

page is Enabled.

For Hardware Switch change events, check that the

HARDWARE

SWITCH REPORTING

parameter on the 2000NET module’s

CONFIGURA-

TION

page is Enabled.

For Frame Bus Failure-Fixed events:

Check that the FRAME BUS switch (Switch 6) on the S1 DIP switch
block of the 2000NET module is Enabled, and

Check that the

FRAME BUS STATUS REPORTING

parameter on the

frame’s

CONFIGURATION

page is Enabled.

For Front Cover Removed -Installed events, check that the

COVER

STATUS REPORTING

parameter on the frame’s

CONFIGURATION

page is

Enabled.

For Frame Bus Failure-Fixed events:

Check that the FRAME BUS switch (Switch 6) on the S1 DIP switch
block of the 2000NET module is Enabled, and

Check that the

FRAME BUS STATUS REPORTING

parameter on the

frame’s

CONFIGURATION

page is Enabled.

For Cooling Fan Failure-Fixed events:

Check that the FAN switch (Switch 4) on the S1 DIP switch block of
the 2000NET module is Enabled, and

Check that the

FAN STATUS REPORTING

parameter on the frame’s

CON-

FIGURATION

page is Enabled.

For Module Health Failure-Fixed events,

Check that the MODULE switch (Switch 5) on the S1 DIP switch