Configuring temperature thresholds for a card – H3C Technologies H3C S12500 Series Switches User Manual
Page 84

74
Configuring temperature thresholds for a card
Step Command
1.
Enter system view.
system-view
2.
Configure temperature
thresholds for a card.
•
In standalone mode:
temperature-limit slot slot-number { inflow | hotspot | outflow }
sensor-num lowerlimit warninglimit [ alarmlimit ]
•
In IRF mode:
temperature-limit chassis chassis-number slot slot-number { inflow |
hotspot | outflow } sensor-num lowerlimit warninglimit [ alarmlimit ]
Displaying the temperature information on your switch
Use the display environment command to display the temperature information of the sensors on the cards,
including the current temperature and temperature thresholds.
# Display the temperature information of the cards on the switch.
•
In standalone mode:
System temperature information (degree centigrade):
-------------------------------------------------------------------------------
Slot Sensor Temperature LowerLimit WarningLimit AlarmLimit ShutdownLimit
0 inflow 1 27 -10 55 80 N/A
0 outflow 1 32 -10 55 80 N/A
0 hotspot 1 32 -10 55 85 N/A
9 inflow 1 34 -10 55 75 N/A
9 outflow 1 34 -10 55 85 N/A
9 hotspot 1 37 -10 55 80 N/A
10 inflow 1 29 -10 55 80 N/A
10 outflow 1 51 -10 55 95 N/A
•
In IRF mode:
System temperature information (degree centigrade):
-------------------------------------------------------------------------------
Slot Sensor Temperature LowerLimit WarningLimit AlarmLimit ShutdownLimit
1/0 inflow 1 27 -10 55 80 N/A
1/0 outflow 1 32 -10 55 80 N/A
1/0 hotspot 1 32 -10 55 85 N/A
1/9 inflow 1 34 -10 55 75 N/A
1/9 outflow 1 34 -10 55 85 N/A
1/9 hotspot 1 37 -10 55 80 N/A
1/10 inflow 1 29 -10 55 80 N/A
1/10 outflow 1 51 -10 55 95 N/A