Super Systems AC20 RS485 Modbus User Manual
Page 38
Page 38/59
TITLE: MODBUS/J-BUS Protocol for SSi’s- AC20 ENG. 824E REV. 1
WORDS FOR DEVICE IN CONFIGURATION MODE - PARAMETERS
“Out.” - Menu Conf. 2 - OUTPUT CONFIGURATION
ADDRESS
(Decimal)
DEC.
Display
R
W
R
Jbus
Mod
Bus
DESCRIPTION
FIGU-
RES
MNEM
CODE
E
A
D
I
T
E
2101
2100
Out 1 function
Range:
0 = Output not used
1 = Time proportional main control output
2 = Time proportional secondary control
output
3 = Output used as alarm 1 output
N.A.
("O1.Fn")
x
x
2102
2101
Out 2 function
Range:
0 = Output not used
1 = Time proportional main control output
2 = Time proportional secondary control
output
3 = Output used as alarm 2 output
N.A.
("O2.Fn")
x
x
2103
2102
Out 3 function
Range:
0 = Output not used
1 = Time proportional main control output
2 = Time proportional secondary control
output
3 = Output used as alarm 3 output
N.A.
("O3.Fn")
x
x
2107
2106
Out 6 function
Range:
0 = Output not used
1 = Linear main control output
2 = Linear secondary control output
3 = Process variable retransmission
4 = Operative set point retransmission
N.A.
("O6.Fn")
x
x
2108
2107
Out 6 range
Range:
0 = 0 ÷ 20 mA
1 = 4 ÷ 20 mA
N.A.
("O6.rn")
x
x
2109
2108
Retransmission low scale range value for
Out 6
See Mbus
word 300
(“O6.Lr”)
x
x
2110
2109
Retransmission high scale range value
for Out 6
See Mbus
word 300
(“O6.Hr”)
x
x
2111
2110
Time constant for filter on Out 6 analog
retransmission value (in seconds)
0
(“O6.FL”)
x