Super Systems AC20 RS485 Modbus User Manual
Page 28

Page 28/59
TITLE: MODBUS/J-BUS Protocol for SSi’s- AC20 ENG. 824E REV. 1
WORDS FOR DEVICE IN CONTROL MODE - NON PARAMETERS
ADDRESS
(decimal)
DEC.
Display
R
W
R
JBus
Mod
Bus
DESCRIPTION
FIGU-
RES
MNEM
CODE
E
A
D
I
T
E
131
130
Main control output value
1
x
x
132
131
Secondary control output value
1
x
x
133
132
Pid out value
1
x
x
134
133
Main control output display value
See Mbus
word 301
(ñ.xxx)
x
135
134
Secondary control output display value
See Mbus
word 302
(S.xxx)
x
136
135
Device status mode
Range:
0 = Control mode
1 = Control mode with error E.130
2 = Control mode with error E.140
3 = Burn-off procedure in progress
4 = Purge procedure in progress
5 = Probe test procedure in progress
6 = Configuration mode
7 = Security code mode
Note:
For E.130/E.140 errors, see Technical
specifications Eng. 247E
The error is reset when read if device is in
remote state
N.A.
x
137
136
Type of operative set point
Range:
0 = The set point utilized is a value set by
serial link (“Operative Set Point
Value”)
1 = Main set point
2 = Auxiliary set point 2
3 = Auxiliary set point 3
4 = Auxiliary set point 4
N.A.
x
138
137
Operative set point value
Note:
It is utilized by the device for the PID as
well as for the SMART algorithms.
Any change will not be influenced by the
gradient mechanism. This set point value
is not going to be stored in Earom and it
will be lost at power down.
See Mbus
word 300
x
x
301
300
Decimal number relative to primary
control variable
N.A.
x
302
301
Decimal number relative to main control
output in engineering units
N.A.
x
303
302
Decimal number relative to secondary
control output in engineering units
N.A.
x