beautypg.com

Super Systems AC20 RS485 Modbus User Manual

Page 26

background image

Page 26/59

TITLE: MODBUS/J-BUS Protocol for SSi’s- AC20 ENG. 824E REV. 1

WORDS FOR DEVICE IN CONTROL MODE - NON PARAMETERS

ADDRESS

(decimal)

DEC.

Display

R

W

R

JBus

Mod

Bus

DESCRIPTION

FIGU-

RES

MNEM

CODE

E
A
D

I

T
E

114

113

Status led alarm 1

Range:

0 = Off
1 = On
2 = Flashing (only for alarm)

N.A.

x

115

114

Status led alarm 2

Range:

0 = Off
1 = On
2 = Flashing (only for alarm)

N.A.

x

116

115

Status led alarm 3

Range:

0 = Off
1 = On
2 = Flashing (only for alarm)

N.A.

x

120

119

Variation on alarm status

Note:

Alarm status information is on D8:
(1 for entrance, 0 for exit)
Number of alarm is on low byte (D2-D0)

N.A.

x

121

120

Manufactured trade mark

Value:

50 (32h)

N.A.

x

122

121

Device identification code

Note:

Nr. of software revision x 100 + identifica-
tion code (43)

N.A.

x

123

122

Probe sensor mV value

Note:

When an error is detected on measure,
the “Data field” contains one of these error
codes:
30004 (7534h) = Under-range
30005 (7535h) = Over-range
30050 (7562h) = Error on internal auto-
zero
30051 (7563h) = Error on internal zero-
integrator

0

x

124

123

Carbon potential value

Note:

When an error is detected on measure,
the “Data field” contains one of these error
codes:
30050 (7562h) = Error on internal auto-
zero
30051 (7563h) = Error on internal zero-

integrator

2

x