beautypg.com

Super Systems AC20 RS485 Modbus User Manual

Page 32

background image

Page 32/59

TITLE: MODBUS/J-BUS Protocol for SSi’s- AC20 ENG. 824E REV. 1

BITS FOR DEVICE IN CONTROL MODE

ADDRESS

(decimal)

Display

R

W

R

JBus

Mod

Bus

DESCRIPTION

MNEM

CODE

E
A
D

I

T
E

212

211

Status tune

Range:

0 = No tune
1 = Tune

x

213

212

Status adaptive

Range:

0 = No adaptive
1 = Adaptive

x

214

213

Lock/unlock status

Range:

0 = Unlock device
1 = Lock device

Note:

See also ModBus word 349

x

217

216

Start probe test procedure

x

218

217

Start burn-off procedure

x

219

218

Local/remote device status

Range:

0 = Device in local
1 = Device in remote

x

x

220

219

Auto/manual function

Range:

0 = Auto
1 = Manual

x

x

222

221

Smart enable/disable

Range:

0 = Disable
1 = Enable

Note:

Reading, this bit is logical OR between Tune
(ModBus bit 211) and Adaptive status
(ModBus bit 212)

(“Sñrt”)

x

x

223

222

Manual reset/acknowledge of an alarm
condition

Range:

0 = No operation
1 = Reset alarm

(“ñ.Rst”)

x

224

223

Load default control parameters value

Range:

0 = No operation
1 = Load default

Note:

The command is accepted only if “Smart”
(ModBus bit 221) is not active.
The default value of group 7 (Serial link pa-
rameters) are not loaded.

x