beautypg.com

Sloan 10xx Slimline Bedpen Washer w/ Royal Flushometer User Manual

Page 5

background image

5

C

Align Flushometer Body and securely tighten first the Tailpiece
Coupling (1), then the Vacuum Breaker Coupling (2), and finally the
Spud Coupling (3). Use a wrench to tighten these couplings in the
order shown.

B

Align Flushometer directly above the Vacuum Breaker Flush
Connection by sliding the Flushometer Body IN or OUT as needed.
Tighten Vacuum Breaker Coupling by hand.

A

Lubricate tailpiece O-ring with water. Insert Adjustable Tailpiece into
Control Stop. Tighten Tailpiece Coupling by hand.

Maximum adjustment of the Sloan Adjustable Tailpiece is 1/2" (13 mm)

IN or OUT from the standard 4-3/4" (121 mm) (centerline of

Flushometer to centerline of Control Stop).

If roughing-in measurement exceeds 5-1/4” (133 mm), consult factory

for longer tailpiece.

NOTE

4¼”

(108 mm)

MIN

5¼”

(133 mm)

MAX

HANDLE ASSEMBLY

A-31 GASKET

TAILPIECE COUPLING

CONTROL

STOP

FLUSHOMETER BODY

G-44 FRICTION RING

VACUUM BREAKER

COUPLING

VACUUM BREAKER

FLUSH CONNECTION

C/L

FIXTURE

C/L

SUPPLY

O-RING

ADJUSTABLE

TAILPIECE

4-1/4”

(121 mm)

A

Make sure Control Stop is CLOSED and remove Flushometer Outer
Cover.

C

Reinstall Outside and Inside
Cover wrench tight. Open
Control Stop to flush supply
line. Close Control Stop and
remove Outside and Inside
Cover.

B

Remove Inside Cover and lift
out Inside Parts Assembly.

D

Reinstall Inside Parts Assembly, Inside Cover and Outside Cover
wrench tight.

CONTROL STOP CAP

H-700-A BAK CHEK

®

CONTROL STOP

D

Install Vandal Resistant
Control Stop Cap onto
Control Stop (Or if you have
a Regal XL, install Control
Stop Plug into Control Stop.).

B

Activate
Flushometer.

A

Open Control Stop COUNTERCLOCKWISE one FULL turn from
closed position.

C

Adjust Control Stop after each flush until the rate of flow delivered
properly cleanses the fixture.

TURN COUNTER-

CLOCKWISE TO OPEN

TURN CLOCKWISE

TO CLOSE

The Sloan Flushometer is engineered for quiet operation. Excessive

water flow creates noise, while too little water flow may not satisfy

the needs of the fixture. Proper adjustment is made when plumbing

fixture is cleansed after each flush without splashing water out from

the lip AND a quiet flushing cycle is achieved.

!!! IMPORTANT !!!

7 - INSTALL FLUSHOMETER

8 - FLUSH OUT SUPPLY LINE

9 - INSTALL CONTROL STOP AND VANDAL RESISTANT STOP CAP OR PLUG