PrimeTest 100

Operating Instructions

16

3.5 Testing an extension lead

• Visually inspect the mains cord and plug for

signs of damage.

Check that the correct fuse is fi tted.

If the cord passes a visual inspection proceed

with the electrical tests.

Plug the supplied 0.5m red IEC lead into the

IEC socket and into a mains outlet on the

extension lead. Plug the mains plug of the

extension lead into the front panel mains socket

.

on the PrimeTest 100.

The extension lead can now be tested in the

same manner as an IEC as described above.

Note:

The protective earth resistance will

depend upon the length of the extension

lead and the size (cross sectional area)

of the cable. The measured value maybe

be acceptable even if a cross is shown

next to the R

PE

enunciator.

Table 1: Approximate resistance of protective
earth conductors.

For further information on protective conductor
resistance and testing of portable appliances can
be found in the Code of Practise for In-service
Inspection and Testing of Electrical Equipment
published by the IEE.

7

1

Cord size / current rating

0.5mm

2

/(3A)

0.20

0.40

1.00

Length

5m

10m

25m

1.0mm

2

/(10A)

0.10

0.20

0.50

1.25mm

2

/(13A)

0.10

0.20

0.40