Seaward 100 PrimeTest User Manual
Page 12

PrimeTest 100
Operating Instructions
10
If there is a fault with the Neutral connection this is
indicated by the display below.
In the event of a test failure, disconnect the
PrimeTest 100 from the supply and rectify the fault.
Do not leave the PrimeTest 100
permanently connected to a mains supply.
The auto switch-off function is disabled
when the PrimeTest 100 is connected
to a live mains socket. The unit will
beep continually after 3 minutes to
remind the user to disconnect from the
mains socket.
3.2 Testing a Class I Appliance
•
Visually inspect the appliance and mains cord
for signs of damage.
• If the appliance passes a visual inspection
proceed with the electrical tests.
•
Plug the earth test lead into the 4mm socket
.
on the PrimeTest 100 end panel.
• Plug the appliance into the PrimeTest 100
front panel mains socket
• Connect the earth test probe to an exposed
metal part on the appliance.
• If the Appliance under test has an ON/OFF
switch, make sure it is in the ON position.
•
Press the Class I test key
•
The PrimeTest 100 will now test the continuity
of the protective earth.
6
1
2