Operational Characteristics 600 lb system

Cycle Times @ Condenser Temp/Cabinet Temp/Water Temp in degrees F

System Pressures @ Condenser Temp/Cabinet Temp/Water Temp in degrees F.

Headmaster maintains a minimum discharge
pressure during freeze of:

·

217 PSIG + 25, -15 PSIG

CPR Valve Setting: 55 - 60 PSIG.

Note: CPR allows a maximum low side pressure at
the CP unit’s compressor. Maximum only occurs
during harvest.

Refrigerant Charge

·

232 oz

Compressor Amps

·

Single Phase - 5 to 7

Batch Weight

·

8 lb

Discharge Pressure Cut Out Switch

·

Cuts Out at: 450 PSIG

·

Resets at: 350 PSIG

Compressor: RS70C1E

Prodigy Eclipse

ä 600, 800, 1000

February 2008

Page 47

70/70/50

90/90/70

120/110/100

Freeze

13 to 15 minutes

16 to 18 minutes

29 to 31 minutes

Harvest

1 to 1.5 minutes

1 to 1.5 minutes

.5 to 1 minutes

70/70/50

90/90/70

120/110/100

Suction at Ice Making Section, end of Freeze

29 to 34 PSIG

30 to 35 PSIG

34 top 39 PSIG

Suction at Ice Making Section, Harvest - peak

103 to 125 PSIG

120 to 140 PSIG

160 to 180 PSIG

Discharge at Condensing Unit: Freeze - 5 min

235 to 255 PSIG

240 to 260 PSIG

345 to 365 PSIG