beautypg.com

Remko cmf / cmt, Technical data, Series – REMKO CMF-120-1P User Manual

Page 58

background image

REMKO CMF / CMT

Series

CMF 120-1P CMT 120-1P CMF 160-1P CMT 160-1P

Function

Heating or Cooling

Inverter technology

REMKO SuperTec

System

Split-Air/Water

Heat pump manager

Multitalent

Storage tank for hydraulic decoupling of volumetric flows

on site

150 l

on site

150 l

Electric booster heating / rated output

kW

optional

Series / 6

optional

Series / 6

Water heating

optional with separate storage technology

Heating output min / max

kW

3,5 - 11,0

5,0 - 16,0

Heating output / compressor frequency / COP

1)

for A10/W35

kW / Hz / -

10,5 / 99 /4,4

15,3 / 76 / 4,7

Heating output / compressor frequency / COP

1)

for A7/W35

kW / Hz / -

10,0 / 96 /4,3

13,0 / 77 / 4,4

Heating output / compressor frequency / COP

1)

for A2/W35

kW / Hz / -

7,2 / 96 /3,4

9,6 / 76 / 3,2

Heating output / compressor frequency / COP

1)

for A2/W35

kW / Hz / -

5,1 / 61 / 3,9

8,0 / 51 / 3,9

Heating output / compressor frequency / COP

1)

for A7/W35

kW / Hz / -

4,8 / 99 /2,5

8,2 / 77 / 2,6

Heating output / compressor frequency / COP

1)

for A15/W35

kW / Hz / -

3,8 / 99 / 1,9

5,43 / 77 / 1,7

Heating output / compressor frequency / COP

1)

for A7/W45

kW / Hz / -

9,4 / 99 / 3,4

13,3 / 76 / 3,4

Heating output / compressor frequency / COP

1)

for A2/W45

kW / Hz / -

7,0 / 96 / 2,8

9,3 / 76 / 2,5

Heating output / compressor frequency / COP

1)

for A7/W45

kW / Hz / -

5,2 / 99 / 2,2

7,4 / 77 / 1,9

Heating output / compressor frequency / COP

1)

for A15/W45

kW / Hz / -

4,3 / 116 / 1,5

4,6 / 77 / 1,2

Heating output / compressor frequency / COP

1)

for A20/W55

kW / Hz / -

10,4 / 94 / 3,0

12,9 / 61 / 3,4

Heating output / compressor frequency / COP

1)

for A7/W55

kW / Hz / -

7,9 / 89 / 2,5

9,4 / 61 / 2,5

Heating output / compressor frequency / COP

1)

for A7/W55

kW / Hz / -

3,1 / 95 / 1,1

6,1 / 77 / 1,3

Cooling output / compressor frequency / EER

2)

for A35/W7

kW / Hz / -

5,4 / 70 / 2,9

12,1 / 74 / 3,1

Cooling output / compressor frequency / EER

2)

for A27/W7

kW / Hz / -

5,9 / 70 / 3,5

12,0 / 69 / 3,7

Service limits, heating

°C

-18 to +34

Service limits, cooling

°C

+15 to +46

Supply-temperature, heating water

°C

up to +60

Refrigerant / pre-charge quantity

-- / kg

R 410A

2)

/ 3.5

R 410A

2)

/ 5.0

Refrigerant / pre-charge quantity for up to 30 m length of ordinary pipe

g/m

60

Max. permissible single refrigerant pipe length

m

50

75

Power supply

V / Hz

230/1~ / 50

400/3~N / 50

Starting current

A

12,5

15

Rated current consumption (for A7/W35)

A

13

15,2

Rated power consumption (for A7/W35)

kW

2,32

2,95

Fuse protection (outdoor unit), characteristic C

A

25

3 x 32

Rated water flow (according to EN 14511, at ∆t 5 K)

m³/h

1,7

2,2

Pressure-loss at the condenser at rated flow

kPa

5,4

8,1

Airflow volume outdoor module

m³/h

3.300

7.200

Max. operating pressure, water

bar

3,0

Hydraulic connection, supply / return

Inches

1“ AG

1“ AG

1“ AG

1“ AG

Sound-pressure level, LpA 1m (outdoor unit)

dB(A)

53/39

3)

56/42

3)

Sound-power level in accordance with DIN EN 12102:2008-09 and ISO 9614-2

dB(A)

64,1

67,1

Dimensions, indoor unit (height/width/depth)

mm

800/550 /550 1760/550/670 800/550/550 1760/550/670

Dimensions, outdoor unit (height/width/depth)

mm

945 / 950 / 330

1338 / 1050 / 330

Protection class outdoor unit

IP 24

IP 24

Weight indoor module

kg

52

135

55

138

Weight outdoor module

kg

75

135

1) COP=coefficient of performance or performance number according to EN 14511
2) Contains greenhouse gas according to Kyoto protocol
3) Clear-field distance: 5m

Technical data

58

This manual is related to the following products: