Remko cmf / cmt, Technical data, Series – REMKO CMF-120-1P User Manual
Page 58
REMKO CMF / CMT
Series
CMF 120-1P CMT 120-1P CMF 160-1P CMT 160-1P
Function
Heating or Cooling
Inverter technology
REMKO SuperTec
System
Split-Air/Water
Heat pump manager
Multitalent
Storage tank for hydraulic decoupling of volumetric flows
on site
150 l
on site
150 l
Electric booster heating / rated output
kW
optional
Series / 6
optional
Series / 6
Water heating
optional with separate storage technology
Heating output min / max
kW
3,5 - 11,0
5,0 - 16,0
Heating output / compressor frequency / COP
1)
for A10/W35
kW / Hz / -
10,5 / 99 /4,4
15,3 / 76 / 4,7
Heating output / compressor frequency / COP
1)
for A7/W35
kW / Hz / -
10,0 / 96 /4,3
13,0 / 77 / 4,4
Heating output / compressor frequency / COP
1)
for A2/W35
kW / Hz / -
7,2 / 96 /3,4
9,6 / 76 / 3,2
Heating output / compressor frequency / COP
1)
for A2/W35
kW / Hz / -
5,1 / 61 / 3,9
8,0 / 51 / 3,9
Heating output / compressor frequency / COP
1)
for A7/W35
kW / Hz / -
4,8 / 99 /2,5
8,2 / 77 / 2,6
Heating output / compressor frequency / COP
1)
for A15/W35
kW / Hz / -
3,8 / 99 / 1,9
5,43 / 77 / 1,7
Heating output / compressor frequency / COP
1)
for A7/W45
kW / Hz / -
9,4 / 99 / 3,4
13,3 / 76 / 3,4
Heating output / compressor frequency / COP
1)
for A2/W45
kW / Hz / -
7,0 / 96 / 2,8
9,3 / 76 / 2,5
Heating output / compressor frequency / COP
1)
for A7/W45
kW / Hz / -
5,2 / 99 / 2,2
7,4 / 77 / 1,9
Heating output / compressor frequency / COP
1)
for A15/W45
kW / Hz / -
4,3 / 116 / 1,5
4,6 / 77 / 1,2
Heating output / compressor frequency / COP
1)
for A20/W55
kW / Hz / -
10,4 / 94 / 3,0
12,9 / 61 / 3,4
Heating output / compressor frequency / COP
1)
for A7/W55
kW / Hz / -
7,9 / 89 / 2,5
9,4 / 61 / 2,5
Heating output / compressor frequency / COP
1)
for A7/W55
kW / Hz / -
3,1 / 95 / 1,1
6,1 / 77 / 1,3
Cooling output / compressor frequency / EER
2)
for A35/W7
kW / Hz / -
5,4 / 70 / 2,9
12,1 / 74 / 3,1
Cooling output / compressor frequency / EER
2)
for A27/W7
kW / Hz / -
5,9 / 70 / 3,5
12,0 / 69 / 3,7
Service limits, heating
°C
-18 to +34
Service limits, cooling
°C
+15 to +46
Supply-temperature, heating water
°C
up to +60
Refrigerant / pre-charge quantity
-- / kg
R 410A
2)
/ 3.5
R 410A
2)
/ 5.0
Refrigerant / pre-charge quantity for up to 30 m length of ordinary pipe
g/m
60
Max. permissible single refrigerant pipe length
m
50
75
Power supply
V / Hz
230/1~ / 50
400/3~N / 50
Starting current
A
12,5
15
Rated current consumption (for A7/W35)
A
13
15,2
Rated power consumption (for A7/W35)
kW
2,32
2,95
Fuse protection (outdoor unit), characteristic C
A
25
3 x 32
Rated water flow (according to EN 14511, at ∆t 5 K)
m³/h
1,7
2,2
Pressure-loss at the condenser at rated flow
kPa
5,4
8,1
Airflow volume outdoor module
m³/h
3.300
7.200
Max. operating pressure, water
bar
3,0
Hydraulic connection, supply / return
Inches
1“ AG
1“ AG
1“ AG
1“ AG
Sound-pressure level, LpA 1m (outdoor unit)
dB(A)
53/39
3)
56/42
3)
Sound-power level in accordance with DIN EN 12102:2008-09 and ISO 9614-2
dB(A)
64,1
67,1
Dimensions, indoor unit (height/width/depth)
mm
800/550 /550 1760/550/670 800/550/550 1760/550/670
Dimensions, outdoor unit (height/width/depth)
mm
945 / 950 / 330
1338 / 1050 / 330
Protection class outdoor unit
IP 24
IP 24
Weight indoor module
kg
52
135
55
138
Weight outdoor module
kg
75
135
1) COP=coefficient of performance or performance number according to EN 14511
2) Contains greenhouse gas according to Kyoto protocol
3) Clear-field distance: 5m
Technical data
58