Remko cmf / cmt, Climatic region: -10°c, Climatic region: -12°c – REMKO CMF-120-1P User Manual
Page 56: Climatic region: -14°c, Climatic region: -16°c

REMKO CMF / CMT
Climatic region: -10°C
Existing buildings with hot-water heating (share 18%)
Type
COP
Annual performance number with inlet/outlet tem-
perature differential: 7K and inlet temperature...
Annual performance number with inlet/outlet tem-
perature differential: 10K and inlet temperature...
A-7/W35
A2/W35
A10/W35
30°C
35°C
40°C
45°C
50°C
55°C
CMF/CMT 120-1P
2,5
3,9
4,4
4,15
4,03
3,82
3,87
3,74
3,60
CMF/CMT 160-1P
2,6
3,9
4,7
4,22
4,09
3,97
3,93
3,80
3,66
New construction with hot-water heating (share 18%)
Type
COP
Annual performance number with inlet/outlet tem-
perature differential: 7K and inlet temperature...
Annual performance number with inlet/outlet tem-
perature differential: 10K and inlet temperature...
A-7/W35
A2/W35
A10/W35
30°C
35°C
40°C
45°C
50°C
55°C
CMF/CMT 120-1P
2,5
3,9
4,4
4,07
3,95
3,91
3,78
3,64
3,50
CMF/CMT 160-1P
2,6
3,9
4,7
4,11
3,99
3,86
3,89
3,68
3,54
Climatic region: -12°C
Existing buildings with hot-water heating (share 18%)
Type
COP
Annual performance number with inlet/outlet tem-
perature differential: 7K and inlet temperature...
Annual performance number with inlet/outlet tem-
perature differential: 10K and inlet temperature...
A-7/W35
A2/W35
A10/W35
30°C
35°C
40°C
45°C
50°C
55°C
CMF/CMT 120-1P
2,5
3,9
4,4
4,07
3,95
3,82
3,79
3,68
3,53
CMF/CMT 160-1P
2,6
3,9
4,7
4,12
4,00
3,88
3,84
3,71
3,58
New construction with hot-water heating (share 18%)
Type
COP
Annual performance number with inlet/outlet tem-
perature differential: 7K and inlet temperature...
Annual performance number with inlet/outlet tem-
perature differential: 10K and inlet temperature...
A-7/W35
A2/W35
A10/W35
30°C
35°C
40°C
45°C
50°C
55°C
CMF/CMT 120-1P
2,5
3,9
4,4
3,98
3,86
3,73
3,69
3,56
3,43
CMF/CMT 160-1P
2,6
3,9
4,7
4,06
3,89
3,81
3,73
3,60
3,46
Climatic region: -14°C
Existing buildings with hot-water heating (share 18%)
Type
COP
Annual performance number with inlet/outlet tem-
perature differential: 7K and inlet temperature...
Annual performance number with inlet/outlet tem-
perature differential: 10K and inlet temperature...
A-7/W35
A2/W35
A10/W35
30°C
35°C
40°C
45°C
50°C
55°C
CMF/CMT 120-1P
2,5
3,9
4,4
4,00
3,89
3,77
3,74
3,61
3,49
CMF/CMT 160-1P
2,6
3,9
4,7
4,10
3,98
3,87
3,79
3,67
3,54
New construction with hot-water heating (share 18%)
Type
COP
Annual performance number with inlet/outlet tem-
perature differential: 7K and inlet temperature...
Annual performance number with inlet/outlet tem-
perature differential: 10K and inlet temperature...
A-7/W35
A2/W35
A10/W35
30°C
35°C
40°C
45°C
50°C
55°C
CMF/CMT 120-1P
2,5
3,9
4,4
3,92
3,80
3,68
3,64
3,52
3,39
CMF/CMT 160-1P
2,6
3,9
4,7
4,00
3,88
3,75
3,68
3,55
3,42
Climatic region: -16°C
Existing buildings with hot-water heating (share 18%)
Type
COP
Annual performance number with inlet/outlet tem-
perature differential: 7K and inlet temperature...
Annual performance number with inlet/outlet tem-
perature differential: 10K and inlet temperature...
A-7/W35
A2/W35
A10/W35
30°C
35°C
40°C
45°C
50°C
55°C
CMF/CMT 120-1P
2,5
3,9
4,4
3,89
3,78
3,67
3,64
3,52
3,39
CMF/CMT 160-1P
2,6
3,9
4,7
3,95
3,84
3,72
3,69
3,57
3,45
New construction with hot-water heating (share 18%)
Type
COP
Annual performance number with inlet/outlet tem-
perature differential: 7K and inlet temperature...
Annual performance number with inlet/outlet tem-
perature differential: 10K and inlet temperature...
A-7/W35
A2/W35
A10/W35
30°C
35°C
40°C
45°C
50°C
55°C
CMF/CMT 120-1P
2,5
3,9
4,4
3,79
3,67
3,56
3,52
3,41
3,28
CMF/CMT 160-1P
2,6
3,9
4,7
3,83
3,72
3,60
3,56
3,45
3,32
Note: A differential of 7K has a standard floor-heating layout, a differential of 10K is typical for a radiator system
Additional key data: a heating-threshold temperature of 15°C for old construction and 12°C in new construction, a differential at the condenser
(test-bench measurements: 5K)
Annual performance number for CMF/CMT 120-1P / CMF/CMT 160-1P
Mode: single energy source, parallel with a switch-over point of -5°C
56