beautypg.com

REMKO CMF-120-1P User Manual

Page 33

background image

In the event that the red control
lamp lights up on the indoor
module, then the fault is on
the outdoor module. Two LEDs
are visible after removing the
enclosure panel which light up
in green and red during normal
operation (see adjacent figure).
If the LEDs flash, then there is a
fault. Causes and measures for
their remedy can be taken from
the following table.

green LED

red LED

Meaning

Remedial measures

flashes 1 times

flashes 1 times

Phase error: The supply cable to the outdoor
module or the connection between the
indoor and outdoor modules is not correct.

Check the electrical connection (swapped
phases)
Check connection cable

flashes 2 times

One of the connectors has been removed
from the PCB or has intermittent contact

Check all connectors on the PCB, check
high and low pressure sensors

flashes 3 times

Fault on PCB

Exchange PCB

flashes 2 times

flashes 1 times

Wiring error between indoor and outdoor
modules

Check connection cable for correct
polarity and proper contact

flashes 2 times

Data transfer error between indoor and
outdoor modules

Check if the connection cable has been
improperly extended or incorrectly
connected

flashes 3 times

flashes 1 times

Hot gas temperature in refrigerant circuit
too high or hot gas heating too low

Check refrigerant; check hot gas
temperature sensor; check expansion
valve

flashes 2 times

High pressure valve has tripped

Open any closed ball valves, check for
excess refrigerant

Low pressure cut-off switch has tripped

Open any closed ball valves, check for
excess refrigerant

No voltage on condenser

Check power supply to the condenser

flashes 3 times

Overheating protection tripped, excessive
liquid temperature in refrigerant circuit

Clean dirty heat exchanger on outdoor
module; rectify possible pneumatic short
circuit on the outdoor device.

flashes 4 times

Circuit breaker on condenser (overload)
has tripped, or no operating voltage at
the condenser

Open any closed spherical valves; check
supply voltage; exchange faulty control
panel

flashes 5 times

Fault in hot gas temperature sensor or fin
temperature sensor (cable breakage or
short circuit)

Check PCB connector for firm connection,
check functionality of the sensor

flashes 6 times

Temperature fault on inverter cooling
block

Rectify obstruction to flow in outdoor
module

flashes 7 times

Fault in power supply

Check and repair power supply

flashes 4 times

flashes 1 times

Fault on liquid line sensor (cable breakage
or short circuit)

Check PCB connector for firm connection,
check functionality of the sensor

flashes 4 times

Temperature of liquid line too high / too
low

Check refrigerant line or
refrigerant level

Flashing code on outdoor module

LEDs

LEDs on outdoor module

33

This manual is related to the following products: