Remko cmf / cmt – REMKO CMF-120-1P User Manual
Page 32
REMKO CMF / CMT
Display
Fault description/note
Heat-
pump fault
(E 54)
Heat pump fault The flow monitor has tripped. A flow problem has occurred. Possible causes
are air in the system, a clogged dirt trap or a defect of the charging pump in the indoor
module. If the red indicator lamp illuminates, there is a problem in the outdoor module which
can only be remedied through customer service.
E 69
Failure or short in supply sensor HK2 (mixing circuit). Sensor F5
E 70
Failure or short inlet pipe WP Multi-purpose sensor 1 Sensor F11
E 71
Failure or short in lower buffer sensor Sensor F12
E 72
Failure or short in upper buffer sensor No assignment by REMKO
E 75
Failure or short, external sensor Sensor F9
E 76
Failure or short, domestic water sensor Sensor F6
E 78
Failure or short, collector sensor Sensor F8
E 80
Failure or short, room sensor heating circuit 1. No assignment by REMKO
E 81
EEPROM error. The valid value has been replaced by the default value. Check parameter
values!
E 83
Failure or short, room sensor heating circuit 2. No assignment by REMKO
E 84
Fault humidity, sensor No assignment by REMKO
E 90
Address 0 and 1 on bus. Bus codes 0 and 1 may not be used simultaneously.
E 91
Bus code assigned. The set bus code is already being used by another device.
E 135
Failure or short, lower WW buffer sensor, multifunction sensor 2. No assignment by REMKO
E 136
Failure or short, heating appliance sensor 2, collector sensor 2, multifunction sensor
3. Sensor F13
E 137
Failure or short in collector sensor 1, multifunction sensor 4. Sensor F14
E 140
Failure or short in return line (cooling-mode control sensor) Sensor F17
E 200 - E 207
Communication heating appliance 1 to WE 7
E 220 - E 253
Communication BM 0 to BM 15
E 240
Communication Manager
E 241
Communication (individual) heating appliances
E 242
Communication mixer
E 243
Communication Solar
customer
service (info
51)
Notice that annual maintenance is needed
Heat-pump
fault (info 55)
Heat pump fault Flow monitor responded or an outdoor-module defect, but only if the
red indicator light also illuminates. If the red indicator light does not illuminate: check the
circulation pump or the flow. There's a possibility of air in the pump or heating circuit
Energy supply
company
switching
Information that the power company has begun an off-period. The heat pump and electric
heating are turned off. A boiler is turned on as needed.
32