Remko wkf duo – REMKO WKF 120 Duo User Manual
Page 52

ID
Description
Details
7210
Open contact - circula-
tion temp. probe S05
Open contact - drinking water circulation temperature probe
7211
Short circuit - circula-
tion temp. probe S05
Short circuit - drinking water circulation temperature probe
7212
Open contact - inlet
temp. probe S13
Open contact - inlet temp. probe
7213
Short circuit - inlet
temp. probe S13
Short circuit - inlet temp. probe
7218
Open contact - collector
1 probe S01
Open contact - collector 1 probe
7219
Short circuit - collector
1 probe S01
Short circuit - collector 1 probe
7236
Open contact - mix.
heating circuit inlet
temp. probe S12
Open contact - mixed heating circuit inlet temperature probe
7237
Short circuit - mix.
heating circuit inlet
temp. probe S12
Short circuit - mixed heating circuit inlet temperature probe
7238
Open contact - mix.
heating circuit return
temp. probe S11
Open contact - mixed heating circuit return temperature probe
7239
Short circuit - mix.
heating circuit return
temp. probe S11
Short circuit - mixed heating circuit return temperature probe
7250
Min. medium flow rate
The medium flow rate fell below the heat generator's minimum medium
flow rate
7251
Min. medium flow rate
The medium flow rate fell below the heat pump's minimum medium flow
rate due to defrosting or in cooling mode. After eliminating the cause of
the error, the controller must be restarted to reset the error.
7252
Heat pump alarm code
S20
Heat pump alarm code
7276
Restart required
Due to the changed system (setting / coding resistor), the controller has
to be restarted - disconnect it from the power supply for around 10 sec-
onds.
7283
Open contact - WE
return temp. probe S15 Open contact - WE return temperature probe
7284
Short circuit - WE
return temp. probe S15 Short circuit - WE return temperature probe
7286
Rc coding error
A unique unit identifier could not be assigned using the coding resistor at
the Rc terminal.
7333
Negative temp. differ-
ence
The temperature difference when the heat generator is active is implau-
sible
REMKO WKF Duo
52