Minimum clearances of the outdoor units
1
2
3
4
5
6
>= 250
>= 1500
>= 1500
>= 250
>= 250
>= 300
>= 600
>= 600
>= 250
>= 1500
>= 2000
Fig. 33: Minimum clearances for installation of an outdoor unit in mm
1:
Next to a wall, air outlet open to the front, flow
restriction behind
2:
Next to a wall, air outlet toward the wall, flow
restriction to the front
3:
Between two walls, air outlet toward the wall,
open sides flow restriction front and rear
4:
In a niche, air outlet open to the front, flow
restriction behind and on both sides
5:
Next to a covered wall, air outlet open to the
front, flow restrictions behind and above
6:
Next to a covered wall, air outlet toward the
wall, flow restrictions behind and above
1
2
3
4
>= 1500
>= 300
>= 600
>= 600
>= 600
>= 250
>= 600
>= 600
>= 1500
>= 250
>= 1500
>= 3000
>= 600
>= 250
>= 3000
Fig. 34: Minimum clearances for installation of multiple outdoor units in mm
1:
Next to a wall, air outlet toward the wall, flow
restriction to the front
2:
In a niche, air outlet open to the front, flow
restriction behind and on both sides
3:
Between two walls, air outlet toward the wall
and to other units, open sides: flow restriction
front and rear
4:
Between two walls, air outlet toward the wall,
sides of outer units open: flow restriction front,
rear and on the sides of the inner units
33