Remko wkf duo – REMKO WKF 120 Duo User Manual
Page 34

Condensate drainage connection and safe
drainage
3
2
4
8
5
5
10
6
7
9
9
11
11
1
Fig. 35: Condensate drainage, seepage of conden-
sate and strip foundation (cross-section)
1:
Outdoor unit
2:
Leg
3:
Condensate catch pan incl. pan heating
4:
Floor bracket
5:
Reinforced strip foundation
HxWxD = 300x200x800mm
6:
Gravel layer for seepage
7:
Drainage channel
8:
Conduit for refrigerant piping and electrical
connecting line (temperature-resistant up to at
least 80°C)
9:
Frost line
10: Drainage pipe
11: Soil
NOTICE!
The refrigerant lines must enter the housing
from the rear, side or front with the use of the
REMKO OA2 oil separator.
WKF/WKF-compact 120/180
E
B
B
A D
C
10
1
5
5
7
1
8
3
F
Fig. 36: Dimensions for the strip foundation (bird's
eye view)
For the designations of 1,3,5,7,8 and 10, please
refer to the legend for the Fig. 35
Dimensions for the strip foundation
(all dimensions in mm)
Dimen-
sion
WKF 120 Duo
WKF 180 Duo
A
800
800
B
200
200
C
620
620
D
370
350
E
400
420
F
100
100
Condensate drainage connection
If the temperature falls below the dew point, con-
densation will form on the finned condenser during
heating mode.
A condensate tray should be installed on the
underside of the unit to drain any condensate.
n
The condensate drainage line should have an
incline of min. 2%. This is the responsibility of
the customer. If necessary, fit vapour-diffusion-
proof insulation.
n
When operating the unit at outside tempera-
tures below 4 °C, ensure the condensate
drainage line is laid to protect it against frost.
The lower part of the housing and condensate
tray is also to be kept frost free in order to
ensure permanent draining of the condensate.
If necessary, fit a pipe heater.
n
Following installation, check that the conden-
sate run off is unobstructed and ensure that the
line is durably leak tight.
REMKO WKF Duo
34