Appendix, 37 hb controller technical guide – Orion System HB Controller User Manual
Page 37

Appendix
37
HB Controller Technical Guide
Appendix
The HB controller has many setpoints that are user-adjustable. This
adjustability allows the installer complete control of all major unit
operating characteristics during the setup and commissioning phase
of the HB unit installation. It also gives a service technician the ability
to change setpoints to monitor and record unit operation to determine
if the unit is functioning as specifi ed. The tables that follow show the
available setpoints for each classifi cation or control group provided on
the HB controller.
Supply Fan Control Setpoints
Description
Min.
Default
Max.
Adj. Two-Speed Fan
-
Two-Speed Fan
-
Low-Speed Fan Signal
1.0 VDC
3.0 VDC
10.0 VDC
High-Speed Fan Signal
1.0 VDC
10.0 VDC
10.0 VDC
Table 5: Supply Fan Control Setpoints
Cooling Control Setpoints
Description
Min.
Default
Max.
Cooling Stages
1
2
2
Minimum Off Time
180 Sec
180 Sec
900 Sec
Minimum On Time
300 Sec
300 Sec
900 Sec
Staging Up Delay Interval
180 Sec
180 Sec
900 Sec
Staging Down Delay Interval
60 Sec
60 Sec
900 Sec
Low Pressure Delay Period
5 Sec
30 Sec
60 Sec
Low Pressure Safety
5 Sec
5 Sec
30 Sec
Low Pressure Max. Trip Point
1
3
5
Fan Off Delay Period
1 Sec
45 Sec
120 Sec
Auto Staging Up Delay
180 Sec
600 Sec
900 Sec
Dehumidify Staging Up Delay
180 Sec
600 Sec
900 Sec
Table 6: Cooling Control Setpoints
Heating Control Setpoints
Description
Min.
Default
Max.
Heating Stages
1
3
3
Minimum Off Time
60 Sec
60 Sec
900 Sec
Minimum On Time
120 Sec
120 Sec
900 Sec
Staging Up Delay Interval
180 Sec
180 Sec
900 Sec
Staging Down Delay Interval
60 Sec
60 Sec
900 Sec
Heat Safety Maximum Count
1
3
5
Fan Off Delay Period
1 Sec
120 Sec
180 Sec
Auto Staging Up Delay
180 Sec
600 Sec
900 Sec
Table 7: Heating Control Setpoints
Temperature Control Setpoints
Description
Min.
Default
Max.
Cooling Lockout Temperature
32ºF
40ºF
80ºF
Heating Lockout Temperature
40ºF
80ºF
120ºF
Supply Air High Temperature
Limit Cutoff
120ºF
150ºF
170ºF
Supply Air Low Temperature
Limit Cutoff
32ºF
40ºF
80ºF
Table 8: Temperature Control Setpoints
Economizer Control Setpoints
Description
Min.
Default
Max.
Econo Confi g
No
Economizer
Max. CO
2
0 PPM
1100 PPM
2000 PPM
Min. CO
2
0 PPM
900 PPM
2000 PPM
Outdoor Air Enable Temp
33ºF
55ºF
65ºF
ECS OAT Enable Temp
55ºF
65ºF
75ºF
Table 9: Economizer Control Setpoints
Exhaust Fan Control Setpoints
Description
Min.
Default
Max.
Low-Speed Supply Fan
0%
50%
100%
High-Speed Supply Fan
0%
30%
100%
Table 10: Exhaust Fan Control Setpoints
Min. Damper Reset Position Setpoints
For Adjustable Two-Speed Fan/CO
2
Description
Min.
Default
Max.
Max. with Low-Speed Fan
0%
50%
100%
Min. with Low-Speed Fan
0%
10%
100%
Max. with High-Speed Fan
0%
30%
100%
Min. with High-Speed Fan
0%
5%
100%
Table 11: Minimum Damper Reset Setpoints