Programming, Programming with the hb service tool – Orion System HB Controller User Manual
Page 28

Zone
Zone
Programming
28
HB Controller Technical Guide
Programming with the HB Service Tool
HB Processor Board
HB Processor Board Status Screens
If your HB Controller is equipped with the HB Processor board, you can
access the available Status and Setpoint screens by using the program-
ming directions that follow.
The Device Address Screen is accessed by pressing the MENU key from
any screen. The current Device Address Screen will be displayed. If the
Current device address is set for 064 (HB Controller Address), you must
change the device address to 066 to access the HB Processor screens.
Press the ADJUST ARROW from Device Address 064 to change to
Device Address 66.
Once the correct Device Address of 066 is displayed as shown above,
press ENTER.
Line #2 displays the HB Processor name. Press the ENTER key to
advance to the HB Processor main status screens. The following screen
will then appear:
Select “Main Status” by pressing the ENTER key. Press the up and
down SELECT arrow keys to move forward and backward through the
Main Status screens.
Date and Time
Line #1 displays the current date inside the HB Processor. Line #2
displays the current time of day inside the HB Processor in 24-hour
format. Press the ENTER key to continue to the next screen.
Schedule Mode
Line #2 displays the current Schedule Mode. Options that may be dis-
played are Occupied, Unoccupied, Force Occupied, Force Unoccupied,
Global Occupied, Global Unoccupied, or Override Occupy. Press the
ENTER key to continue to the next screen.
HVAC Mode
Line #2 displays the current HVAC Mode when Space Temperature
Control is confi gured. Options that may be displayed are Idle, Vent-
ing, Heating, or Cooling. Press the ENTER key to continue to the next
screen.
Space Temperature
Line #2 displays the current Space Temperature. Press the ENTER key
to continue to the next screen.
Cooling Setpoint
Line #2 displays the current Cooling Setpoint. Press the ENTER key to
continue to the next screen.
Heating Setpoint
Line #2 displays the current Heating Setpoint. Press the ENTER key to
continue to the next screen.
H/C Demand
Line #2 displays the demand for Heating or Cooling based on the Space
Temperature in reference to the Heating or Cooling setpoint. Press the
ENTER key to continue to the next screen.
Override Left
Line #2 displays the Override Time remaining once the Push-Button
Override on the Space Temperature Sensor has been activated. Press
the ENTER key to continue to the next screen.