Programming, Programming with the hb service tool, 19 hb controller technical guide – Orion System HB Controller User Manual
Page 19

Programming
19
HB Controller Technical Guide
Condenser Fan Deactivation Temperature
The Condenser Fan Deactivation Temperature is a factory setting and
should not be changed unless authorized to do so by WattMaster or
AAON
®
Technical Support.
Auto Stage-Up Time
Description
Min.
Default
Max.
Auto Staging Up Delay
180 Sec
600 Sec
900 Sec
The Auto Stage-Up Time can be adjusted on this screen when you are
using a single-stage thermostat with a multi-stage HB unit.
Heating Module Status Screens
The Heating Module Status Screens are accessed by navigating to the
Heating Module screen and pressing the ENTER key. The following
screen will then appear:
Select “Status” by pressing the ENTER key. Press the up and down
SELECT arrow keys to move forward and backward through the Heat-
ing Module Status screens.
Heating Stage 1 Energized
Line #2 displays “YES” if there is a 24 VAC signal on HB Controller
terminal “W1.”
Heating Stage 2 Energized
Line #2 displays “YES” if there is a 24 VAC signal on HB Controller
terminal “W2.”
Low Pressure Switch Delay
Description
Min.
Default
Max.
Low Pressure Delay Period
5 Sec
30 Sec
60 Sec
The Low Pressure Switch Delay time is a factory setting and should
not be changed unless authorized to do so by WattMaster or AAON
®
Technical Support.
Low Pressure Switch Safety Delay
Description
Min.
Default
Max.
Low Pressure Safety
5 Sec
5 Sec
30 Sec
The Low Pressure Switch Safety Delay time is a factory setting and
should not be changed unless authorized to do so by WattMaster or
AAON
®
Technical Support.
LPS Maximum Trips
Description
Min.
Default
Max.
Low Pressure Max. Trip Point
1
3
5
The Low Pressure Switch Max Trips is a factory setting and should
not be changed unless authorized to do so by WattMaster or AAON
®
Technical Support.
Cooling Fan Off Delay
Description
Min.
Default
Max.
Fan Off Delay Period
1 Sec
45 Sec
120 Sec
The Cooling Fan Off Delay is a factory setting and should not be
changed unless authorized to do so by WattMaster or AAON
®
Techni-
cal Support.
Condenser Fan Activation Temperature
The Condenser Fan Activation Temperature is a factory setting and
should not be changed unless authorized to do so by WattMaster or
AAON
®
Technical Support.
Programming with the HB Service Tool