Programming, Programming with the hb service tool, 20 hb controller technical guide – Orion System HB Controller User Manual
Page 20

Zone
Zone
Programming
20
HB Controller Technical Guide
Heating Stage 3 Energized
Line #2 displays “YES” if there is a 24 VAC signal on HB Controller
terminal “W3.”
Fan Status
Line 2 displays the current Supply Fan Status. If the Supply Fan is on,
line #2 displays either “Fan Low Speed” or “Fan High Speed.”
Fan Signal
Line #2 displays the current Supply Fan Analog Output Signal in DC
Volts.
Heating Relay #1
Line #2 displays “ON” if Heating Relay #1 is active.
Heating Relay #2
Line #2 displays “ON” if Heating Relay #2 is active.
Heating Relay #3
Line #2 displays “ON” if Heating Relay #3 is active.
Heat Safety Monitor
Line #2 displays “OPEN” anytime the Heat Safety Monitor is open.
Heating Module Setpoint Screens
The Heating Module Setpoint Screens are accessed by navigating to
the Heating Module and then pressing the ENTER key. The following
screen will then appear:
Press the down SELECT arrow key until “Setpoints” is on the top line
of the screen and then press the ENTER key. Press the up and down
SELECT arrow keys to move forward and backward through the Heat-
ing Module Setpoint screens.
Heating Stages Quantity
Description
Min.
Default
Max.
Heating Stages
1
3
3
Adjust the quantity of Heating Stages and then press the ENTER key.
Outdoor Air Temperature Heating Lockout
Description
Min.
Default
Max.
Heating Lockout Temperature
40ºF
80ºF
120ºF
Adjust the Outdoor Air Temperature Heating Lockout and then press
the ENTER key.
Low Supply Air Temperature Cutoff
Description
Min.
Default
Max.
Supply Air Low Temperature
Limit Cut Off
32ºF
40ºF
80ºF
Adjust the Low Supply Air Temperature Cutoff and then press the
ENTER key.
High Supply Air Temperature Cutoff
Description
Min.
Default
Max.
Supply Air High Temperature
Limit Cut Off
120ºF
150ºF
170ºF
Adjust the High Supply Air Temperature Cutoff and then press the
ENTER key.
Programming with the HB Service Tool