SynPur
Mounting rail
Product
Infeed
Synthesizing stages
Additive
Figure 3: Basic System B with two synthesizing stages
3.1.3 Conductivity Synthesizer with existing full deionization stage
If a full deionization stage already exists in a plant for generating fully deionized
water (DI water), the DI water can be connected directly to the mounting rail. The
synthesizer cartridges are not required in this case. This system consists of a
mounting rail, an SynPur, and the additive. The connection to the synthesizer
cartridge should be jumpered on the mounting rail (see Figure 3).
Requirements of the DI water:
-
Conductivity < 0.1µS
-
Constant flow pressure of 2-3 bar (29-43.5 psi)
-
Freedom from organic components (< 100 KBE)
Deionized water in untreated form is not suitable for use in a single-component air
humidification system. The SynPur conditions the DI water in such a way that it can
be used without reservation.