4 material specification – Nortec SynPur User Manual
Page 24
Created: 21.12.2006
Changed: 21.03.2007
Printed: 02.03.2009
page 24 of 37
4.4 Material specification
4.4.1 Electrical components
Electrical cables
Purpose:
From the SynPur to the HPS
Designation:
LIYY 7x 0.75 mm
2
(color or number code), AWG 18
Capacity:
Purpose:
From the SynPur to the GLT
Designation:
LIYY 4x0.75 mm
2
(color or number code), AWG 18
Capacity:
Standard plug with grounding connections (wall-mounted)
Purpose:
Conductivity Synthesizer, SynPur
Techn. data:
LS3400:
230 VAC, 16 A, L1, N, PE
LS3402:
120 VAC, 16 A, L1, N, PE
4.4.2 Additive
Designation:
Carbon dioxide, CO
2
Purity:
99.5%
Type of gas:
Technical gas
4.4.3 Pressure reducer
Designation:
Is fixed directly at the CO
2
-bottle
Techn. Daten:
- Back pressure 8 bar (116 psi)
- Operating pressure 6 bar (87 psi)
- The safety valve must be adjusted at 10-12 bar (145-174
psi).
-
The output, connection to console, must have a ¼“ threat
(male).