TROUBLESHOOTING (cont.)
If conditions persist after the above remedies have been performed, turn off the
unit, disconnect the power, and contact your MovinCool reseller or a qualified
technician.
Condition
Self-
Diagnostic
Codes
(Wall
mounted
controller)
Buzzer
Pattern
Possible
Cause
Remedy
Unit
does
not
operate.
LCD
displays
self-
diagnostic
codes.
E01
Defective RTS1
thermistor
(short or open)
Replace the wall
mounted controller.
Press RESET
button, then press
ON/OFF button.
E02
2
Loose RTS2
thermistor
connection
Connect the
connector securely.
Press RESET
button, then press
ON/OFF button.
Defective RTS2
thermistor
(short or open)
Replace RTS2
thermistor.
Press RESET
button, then press
ON/OFF button.
E03
2
Loose EWTS
thermistor
connection
Connect the
connector securely.
Press RESET
button, then press
ON/OFF button.
Defective EWTS
thermistor
(short or open)
Replace EWTS
thermistor.
Press RESET
button, then press
ON/OFF button.
E04
2
Loose CTS1
thermistor
connection
Connect the
connector securely.
Press RESET
button, then press
ON/OFF button.
Defective CTS1
thermistor
(short or open)
Replace CTS1
thermistor.
Press RESET
button, then press
ON/OFF button.