Installation (cont.), Water pipe connection (cont.) – MovinCool CMW30 User Manual
Page 17

17
INSTALLATION (cont.)
Water Pipe Connection (cont.)
Connecting Water Pipes (cont.)
4. Make sure the water inlet and outlet of the unit and water source are
connected, and there is no water leakage.
CAUTION: Supply water pressure limitation is maximum 150 psi
(1,034 kPa). Do not use the unit with water which contains a high
corrosive factor.
5. Attach the insulators to the water pipes and connectors to prevent
condensation.
CAUTION: If the insulators are not attached properly, condensation
may occur.
Note:
1. Service shut-off valves and drain plugs are recommended to be installed at the
water supply and return lines for routine field service or emergency service.
The drain plugs are used to drain the remaining water in the system. The shut-
off valves and drain plugs should have a minimum pressure rating of 150 psi
(1,034 kPa). The drain plugs should be connected between the shut-off valves
and the unit.
2. When supply water quality is poor, filters that can be easily serviced should be
placed in the water supply line.
ILL00333-00