INSTALLATION (cont.)

Drain Hose Connection

The CMW30 is equipped with an

internal condensation removal pump

with maximum head lift of 4 feet (1.2 m).
1. Use the provided 1/2 inch (13 mm)

male connection on the unit for the

evaporator coil condensate drain.

The drain line must be located so it

will not be exposed to freezing

temperatures. The drain should be

the full size of the drain connection.

(Connect the drain hose to the

condensation drain or the janitor closet.)

2. PVC tubing (1/2 inch (13 mm) for ID, 5/8 inch (16 mm) for OD) is required for

the drain. Insulate the drain hose. Condensation may occur during humid

conditions.

Note: PVC tubing and insulation material are field supplied.

Note: Do not use more than 4 feet (1.2 m) of drain hose vertically. This is maximum

lift of the condensation pump.
3. To insure proper drainage, locate the drain hose to the highest vertical position,

no more than 4 feet (1.2 m) high, and run the hose to the drain on a downward

slope at a minimum rate of 1/4 inch (6 mm) per foot.

1. Plug in the 1/2 inch (13

mm) drain hose with the

supplied clip into the drain

pipe. Make sure the hose

is all the way in and flush

with the grommet.

2. Position the clip to the top

of the drain pipe near the

unit as shown.

3. Pull out the stopper and

secure hose. Make sure

there are no kinks or bends.

When using the gravity

drain, make sure the hose

is connected as a decline.

DRAIN PIPE

CONDENSATE PAN DRAIN

FOR GRAVITATIONAL

DRAIN/MAINTENANCE

ILL00262-00

ILL00263-00

ILL00264-00

STOPPER

ILL00265-00

MAX. 3 ft

(0.9 m)

MAX. 4 ft (1.2 m)

1/4 in (6 mm)

PER FOOT

OR MORE

ILL00266-00