Troubleshooting (cont.) – MovinCool CMW30 User Manual

Page 53

background image

53

TROUBLESHOOTING (cont.)

If conditions persist after the above remedies have been performed, turn off the

unit, disconnect the power, and contact your MovinCool reseller or a qualified

technician.

Condition

Self-

Diagnostic

Codes

(Wall

mounted

controller)

Buzzer

Pattern

Possible

Cause

Remedy

Unit

does

not

operate.

LCD

displays

self-

diagnostic

codes.

AL

1

Signal is input to

the fire alarm

connection.

Connect the fire

alarm signal wires

correctly.

(See “Fire Alarm

Connection (Input

Signal) on page 35”.)

Press RESET

button, then press

ON/OFF button.

PU

3

Drain hose clogged

(for internal drain

pump).

Remove any

blockages or

excessive kinks

preventing water

flow.

Press RESET

button, then press

ON/OFF button.

Drain hose trap

position is too high

to pump up

condensation water

(for internal drain

pump).

Improve hose

installation.

(See “Drain Hose

Connection” on

page 18 to 19.)

Press RESET

button, then press

ON/OFF button.

Internal drain pump

is not working.

Connect the internal

drain pump

connector securely.

Press RESET

button, then press

ON/OFF button.

If the internal drain

pump still does not

work, replace it.