Installation

Section 6: Finishing Around the Fireplace

Combustible mantels and mouldings may be safely installed over the

top and on the front of the fireplace provided that they do not project

beyond shaded area shown in Figure 22.

Fireplace Facing

When sizing the finish material for your fireplace, it is important to

remember the following: THE OPENING MUST NOT BE OBSTRUCTED

IN ANY WAY - to do so restricts the air supply for the control

compartments and heat exchanger it also prevents access for

servicing controls�
The face of the fireplace may be painted to match the room decor,

provided you use a heat-resistant paint. Decorative facing must not

extend past the fireplace opening at all, because it will interfere with

the access to retainers for removal of glass door.

Mantels & Surrounds

NOTE: National Canadian Gas Association mantel test requirements

are for fire hazard prevention to combustible materials.
Side wall clearances are 3". Combustible surrounds may be installed

with 3" clearance to the side of the fireplace.

Do not operate this fireplace without the glass door or with a broken glass door.

NOTICE

Do not use ammonia based or abrasive cleaners on the glass, they will permanently

etch the surface. Use an approved gas fireplace glass cleaner such as Kel-Kem or

White off.

NOTICE

WARNING!

We recommend careful consideration be given to the effects of

elevated mantel temperatures which may be in excess of product

design, for example: candles, plastic or pictures. This can cause

melting, deformation, discolouration or premature failure of T.V.

radio, and other electronic components.

WARNING!

When covering the upper metal portion of the fireplace, up to 4"

(as shown, Fig.22) with a non-combustible material Please Note:

The decorative facing materials may be subject to temperatures

in excess of 250° F. This should be considered when selecting

facing materials.

Combustible

Construction allowed

in shaded area

Top of fireplace

4” Nailing flange

Combustible Facing

Material

Horizontal Run (in)

Vertica

l Run (in)

Steel Stud construction

allowable within grey area

Figure 22� Combustible mantels and facings.

Figure 23� Combustible surrounds.

WARNING

Do not place any materials or objects on top of the

valve blind. Doing so could result in failure of door

relief system or heat dissipation.

4” Nailing Flange

Drywall/Sheetrock

3”

Header