beautypg.com

Installation – Montigo B34DV User Manual

Page 11

background image

Page 11

B-Series DV-2 Gas Fireplace

Part No. XG0160 - 141231

Installation

Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 84" and the horizontal

run to the wall flange of the vent termination is 30", this would be

an acceptable installation.

Example B: (Acceptable Installation)

If the vertical dimension from the hearth is 108" and the horizontal

run to the wall flange of the vent termination is 120", this would be

an acceptable installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 72" and

the horizontal run to the wall flange of the vent termination is 84",

this would NOT be an acceptable installation.

B. Multi-Elbow Installations

For more difficult installation situations, the B-Series DV-2 Rear Vent

may be installed with two - 90° elbows and up to 15' of horizontal run. If

using this installation option, you must adhere to the following guidelines:
Important: Some models are not available to be installed in a rear

vent application. Please refer to the model specifications on page

2 of this manual.

the first 90° elbow must be placed directly on the flue collar

you must have a minimum vertical lift of 50" (measured from the

hearth)

your vent run must fall within the limits set by Figure 20.

Before you install any venting, you must determine whether the venting

run will be acceptable. Unacceptable venting can affect the fireplace's

combustion.

The Venting Graph

Measure the vertical height from the fireplace hearth to the centre of

the termination and the horizontal run from the from the fireplace flue

collar to the wall flange of the termination. Plot on the Venting Graph

(Fig. 20) with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the

installation is acceptable.

Figure 20. B-Series DV-2 Multi-Elbow Venting Graph.

NOTES:

All dimension lengths for vertical or horizontal runs are

measured from center of the vent pipe.

Venting runs must fall within the limits set by the venting

graph (see Figure 20).

B

A

32”

C

50”

18"

Max.

15’ Max.

50"

Min.

Figure 21. Multi-elbow installation. (For the B-Series the vertical

distance must be a minimum of 50". The vent run must

comply with the Graph, figure 20).

4" / 7" Venting

A - Termination

MTO-4 (3" Length)

MTO-4F (3" Length)

B - Stucco Kits

MSR (Stucco Frame)

BSR-4 (4" Brick Frame)

BSR-6 (6" Brick Frame)

MOSR (Stucco Can)

C - Flex Sections MFL-1 (12" Section)

MFL-2 (24" Section)

MFL-3 (36" Section)

MFL-4 (48" Section)

D - Rigid

Sections

MEXT-1 (12" m/f Section)

EXT-18 (18" f/f section)

MEXT-2 (24" m/f Section)

MEXT-3 (36" m/f Section)

MEXT-4 (48" m/f Section)

E - Elbows MEL-90MM (m/m 90° Elbow)

MEL-90FF (f/f 90° Elbow)

MEL-90FM (f/m 90° Elbow)

EEL-45 (f/m 45° Elbow)

MFL-6 (72" Section)

MEXT-6 (72" m/f Section)

Installation of Rear Vent DV-2

The following venting components are available from a B-Series DV-2

in a Rear Vent Installation:

This manual is related to the following products: