Clearances, Installing the standoffs, Installing the nailing flange extension – Montigo H38DF User Manual
Page 8: Installation

Page 8
XG0147 - 150204.1
H*38DF Gas Fireplace
Installation
6”
Clearances
When installing a shelf over the top of the fireplaces, the following
guidelines must be adhered to:
For Rear Vent applications, the minimum clearance is 2" from the rear
of the fireplace to a wall, or any combustible materials, and 9" clearance
from the top of the fireplace to the underside of any combustible shelf
materials.
For Top Vent applications, the minimum clearance is 2" from the rear of
the fireplace to a wall, or any combustible materials, and 17 1/2" to the
underside of any combustible shelf materials, Figure 4.
For Top or Rear Vent applications where the Minimum height is required
above the fireplace, (for an alcove or low profile shelf), ALL Materials
MUST BE NON-COMBUSTIBLE, Figure 5. The minimum clearance is
2" from the rear of the fireplace to a wall, or any combustible materials.
1” clearance is maintained on sides and bottom of vent runs and 2”
above horizontal vent runs to any combustible material.
The fireplace clearances are shown below:
H*38DF
9 17 1/2 2 1
0
See Section 6:
Finishing around
the fireplace
HW38DF
9 17 1/2 3 1
0
MODEL
Top - Rear V
ent
†
Installing The Standoffs
To avoid elevated mantel temperatures, all H*38DF* gas
fireplaces are required to have the supplied standoffs installed.
The fireplace is supplied with two standoffs. Bend and install these
standoffs on top of the fireplace ensuring that the height of the standoff
maintains a 6" clearance.
Figure 6. Installing the standoff's.
Figure 7. Installing the Nailing Flange Extension.
Installing the Nailing Flange Extension
Once the fireplace is placed into the rough framed opening, the supplied
Nailing Flange Extension (Part No. H38074) must be fasten securely
into place, with nails or wood screws. as shown in Figure 7.
Note: The nailing flange extension can be substituted with a piece of
NON-Combustible material of the same size and thermal characteristics,
ie: cement board or equivalent. This is recommended in applications
where the facing materials will not adhere to the metal nailing flange.
6"
† Note: Clearance from top of fireplace to a ceiling within the fireplace
enclosure.
Top - T
op V
ent
†
Rear
Sides
Floor
Mantel