H*38DF Gas Fireplace
XG0147 - 150204.1
Maintenance
Maintenance
Lighting Instructions
See pages 27 to 29.
CAUTION!
Fireplace gas control must be in the “OFF” position and pilot
and main burners extinguished when cleaning appliance with
a vacuum.
Doors can get very hot. Handle only when cool.
Cleaning
When the fireplace is first activated, there may be some smoking and
a visible film may be left on the glass. This is a normal condition, and is
the result of burning of protective coatings on new metal.
Glass must be cleaned periodically to remove any film (which
is a normal by-product of combustion) which may be visible.
Film can easily be removed by removing the door, as shown on
Page 22. Handle the door carefully, and clean it with nonabrasive
glass cleaners. One of the most effective products is Kel Kem.
Silicone seals on inner door during initial firing will "off gas",
leaving a visual deposit of a white substance on combustion
chamber walls. This can easily be removed from the chamber
walls using normal household products.
Use a vacuum cleaner or whisk broom to keep the control
compartment, burner, and firebox free from dust and lint.
Logs may be cleaned periodically with a vacuum to remove soot
or other contaminates.
Hi-Lo Burner Adjustment: (SIT Nova 820).
The H*38DF* is equipped with an adjustable burner, allowing you to
raise or lower the flames. To adjust the flames, locate the black knob
marked 'Hi-Lo', in the centre of the gas control valve (See Figure 32).
To raise the flame height, turn the black knob (located behind the
lower control compartment) counter-clockwise.
To lower the flame height, turn clockwise.
Figure 32. 'Hi-Lo' Adjustment on the SIT Nova 820 gas valve,
Hi-Lo Burner Adjustment: (SIT Proflame 2).
The H*38DFI is equipped with an adjustable burner, allowing you to
raise or lower the flames. To adjust the flames, locate the black knob
marked 'Hi-Lo', in the centre of the gas control valve (See Figure 33).
To raise the flame height, turn the black knob (located behind the
lower control compartment) counter-clockwise.
To lower the flame height, turn clockwise.
Figure 33. 'Hi-Lo' Adjustment on the SIT Proflame 2 gas valve.
Manifold Pressure
Test Connection
Pilot Adjustment Screw
Hi Lo Adjustment
Inlet Pressure
Test Connection
Pilot Burner Adjustment.
1. Locate Pilot Adjustment Screw. (See figure 32 or 33.)
2. Adjust pilot screw to provide properly sized flame as shown.
3. After installing or servicing, leak test with a soap solution with main
burner on. Coat pipe and tubing joints, gasket etc. with soap solution.
Bubbles indicate leaks. Tighten any areas where the bubbles appear
until the bubbling stops completely.
Manifold Pressure
Test Connection
Wall Switch
Power
Generator
Pilot Adjustment Screw
Inlet Pressure
'Hi-Lo' Adjustment Knob
Gas Control Knob (Shown in “Pilot” position)
For Natural Gas this appliance requires a minimum inlet pressure
of 5.5" W.C. and a manifold pressure of 3.5" W.C.
For Propane Gas this appliance requires a minimum inlet
pressure of 11" W.C. and a manifold pressure of 10" W.C.
Always keep the fireplace area clear and free of combustible
materials, as well as gasoline and other flammable vapours
and liquids.
Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and any
gas control which has been under water.
General
Have the fireplace and installation inspected yearly. The inspection
must include, but is not limited to, the following:
• A visual check of the entire vent system and termination.
• An inspection of the explosion relief flappers and the door
gaskets to ensure a proper seal.
• An inspection of the burner, vent run, and primary air openings.
• An inspection of the gas valve, gas components, and pilot flame.
For your convenience a 1/8" manifold pressure tap is supplied
on the gas valve for a test gauge connection.
• Ensure proper log placement as per this manual.
• Inspection of all optional equipment; fans, thermostats, etc.
• Inspection of all glass doors and screen for damage and proper
installation