Microsonic lcs-25/DD/QP User Manual
B7300, Instruction manual, Lcs-ultrasonic sensors with two switched outputs
Sensor adjustment with Teach-in procedure
Adjust detect point D1
Place object at position
Adjust window mode D1
Place object at position
Adjust two-way reflectiv
barrier D1
Place reflector at position
Set NOC/NCC D1
Adjust detect point D2
Place object at position
Adjust window mode D2
Place object at position
Adjust two-way reflectiv
barrier D2
Place reflector at position
Set NOC/NCC D2
Connect Com to +U
B
until both
LEDs flash simultaneously
(ca. 3 s)
Both LEDs:
flash
mutually
Connect Com to +U
B
for about 1 s
Connect Com to +U
B
until both
LEDs flash simultaneously
(ca. 3 s)
Both LEDs:
Place object at position
flash
mutually
Beide LEDs:
Connect Com to +U
B
for about 1 s
blinken
wechselseitig
Connect Com to +U
B
until both
LEDs flash simultaneously
(ca. 3 s)
Both LEDs:
flash
mutually
Connect Com to +U
B
until both
LEDs flash mutually
(ca. 13 s)
LED D1:
LED D2:
Connect Com to +U
B
for about 10 s
To change output characteristic
connect Com to +U
B
for about 1 s
Wait for 10 s
on: NOC
off: NCC
flashes
Connect Com to -U
B
until both
LEDs flash simultaneously
(ca. 3 s)
Both LEDs:
flash
mutually
Connect Com to -U
B
for about 1 s
Connect Com to -U
B
until both
LEDs flash simultaneously
(ca. 3 s)
Both LEDs:
Place object at position
flash
mutually
Beide LEDs:
Connect Com to -U
B
for about 1 s
blinken
wechselseitig
Connect Com to -U
B
until both
LEDs flash simultaneously
(ca. 3 s)
Both LEDs:
flash
mutually
Connect Com to -U
B
until both
LEDs flash mutually
(ca. 13 s)
LED D2:
LED D1:
Connect Com to -U
B
for about 10 s
To change output characteristic
connect Com to -U
B
for about 1 s
Wait for 10 s
on: NOC
off: NCC
flashes
Normal mode operation
Normal mode operation
1
1
2
1
85 %
1
1
2
1
85 %
Instruction manual
lcs-Ultrasonic Sensors with
two switched outputs
lcs-25/DD/QP
lcs-35/DD/QP
lcs-130/DD/QP
Product description
The lcs-sensor with two switched outputs
measures the distance to an object within
the detection zone contactless. Depending
Ultrasonic Sensors
on the adjusted detect distance the switched
outputs are set.
The output functions are changeable
from NOC to NCC.
Light emitting diodes (three-colour
LEDs) indicate the switching status.
The sensors can be trained using Teach-
in processes.
Using the LinkControl adapter (optional
accessory) all sensor parameter settings
may be made by a Windows-Software.
Important instructions for assembly and
application
All employee and plant safety-relevant
measures must be taken prior to assembly,
start-up, or maintenance work (see operation
manual for the entire plant and the operator
instruction of the plant).
The sensors are not considered as safety
equipment and may not be used to ensure
human or machine safety!
The lcs-sensors indicate a blind zone, in
which the distance cannot be measured. The
operating range indicates the distance of the
sensor that can be applied with normal re-
flectors with sufficient function reserve.
When using good reflectors, such as a calm
water surface, the sensor can also be used up
to its maximum range. Objects that strongly
absorb (e.g. plastic foam) or diffusely reflect
sound (e.g. pebble stones) can also reduce
the defined operating range.
Assembly instructions
Assemble the sensor at the installation
location.
Plug in the connector cable to the M 12
connector.
Fig. 1: Pin assignment with view onto sensor
plug and colour coding of the
microsonic connection cable
Assembly distances
The assembly distances shown in Fig.2 for
two or more sensors should not be fallen
below in order to avoid mutual interference.
Fig. 2: Assembly distances
1
3
colour
+U
B
-U
B
brown
blue
4
2
5
D2
D1
black
white
Com.
grey
1
5
2
3
4
>10 cm
>30 cm
>1,0 m
>1,7 m
>60 cm
>5,4 m
A
B
Start-up
lcs sensors are delivered factory made with
the following settings:
Switched outputs on NOC
Detecting distances at operating range
and half operating range
Measurement range set to maximum
range
Set the parameters of the sensor using the
Teach-in procedure.
Operation
lcs- sensors work maintenance free. Small
amounts of dirt on the surface do not influ-
ence function. Thick layers of dirt and caked-
on dirt affect sensor function and therefore
must be removed.
Note
mic+sensors have internal temperature
compensation. Because the sensors heat
up on their own, the temperature com-
pensation reaches its optimum working
point after approx. 30 minutes of opera-
tion.
During normal mode operation, a yel-
low LED signals that the corresponding
switched output has connected.
During Teach-in mode, the hysteresis
loops are set back to factory settings.
If no signal is transmitted to the Com
input for 20 s during parameter setting
mode the made changes are stored and
the sensor returns to normal mode ope-
ration.
You can reset the factory settings at any
time, see »Lock Teach-in & factory set-
ting«
.
lcs-sensors optional can be programmed
using the LinkControl adapter LCA-2,
see «Optional setting of parameters
using the LinkControl Adapter LCA-2».
*B7300*
MV-DO-074380-234282
Set switched output D1
Set switched output D2
2004/108/EC
Lock Teach-in & factory setting
Activate/deactivate
Teach-in
Reset to factory
setting
Turn supply voltage OFF
While Com is connected
to -U
B
turn on
power suply
Turn supply voltage OFF
While Com is connected
to -U
B
turn on
power suply
Keep Com connected to
-U
B
until both LEDs flash
simultaneously
(ca. 3 s)
LED D1:
LED D2:
on: Teach-in
activated
off: Teach-in
deactivated
flashes
To activate or
deactivate Teach-in
connect Com to -U
B
for
about 1 s
Wait for 10 s
Keep Com connected to
-U
B
until both LEDs
stop flashing
(ca. 13 s)
Normal mode operation