Microsonic pico+15/I User Manual
Ultrasonic sensors
Operating Instructions
pico+15/I
pico+15/WK/I
pico+25/I
pico+25/WK/I
pico+35/I
pico+35/WK/I
pico+100/I
pico+100/WK/I
pico+15/U
pico+15/WK/U
pico+25/U
pico+25/WK/U
pico+35/U
pico+35/WK/U
pico+100/U
pico+100/WK/U
Ultrasonic sensor with one ana-
logue output
Product Description
The pico+sensor offers a non-contact
measurement of the distance to an
object that has to be present within
the sensor’s detection zone. Depend-
ing on the set window limits, a dis-
tance-proportional analogue signal is
output.
The window limits of the analogue
output and its characteristic can be
adjusted with the Teach-in proce-
dure.
Two LEDs indicate operation and the
state of the analogue output.
Safety Notes
Read the operating instructions
prior to start-up.
Sensor adjustment with Teach-in procedure
Set window
margins
Place object at position
Connect Com for about
3 s to +U
B
, until both LEDs
flash simultaneously
Both LEDs:
Place object at position
flash alternately
Set rising/falling output
characteristic curve
Connect Com for about
13 s to +U
B
, until both
LEDs flash alternately
Green LED:
Yellow LED:
flashes
on: rising,
off: falling
characteristic
curve
Switch
Teach-in / synchronization
Switch off power supply
Reset to factory setting
Switch off power supply
Connect Com to -U
B
Switch on power supply
Keep Com connected to
-U
B
for about 3 s, until
both LEDs flash
simultaneously
Green LED:
Yellow LED:
flashes
on: Teach-in
off: synchro-
nization
Connect Com to -U
B
Switch on power supply
Keep Com connected to
-U
B
for about 13 s, until
both LEDs stop flashing
Disconnect Com from -U
B
before switching off
power supply
Connect Com for about
1 s to +U
B
Normal operating mode
To change output
characteristic connect
Com for about 1 s to +U
B
Wait for about 10 s
To change operation mode
connect
Com for about 1 s to -U
B
Wait for about 10 s
Normal operating mode
Connection, installation and
adjustment works should be car-
ried out by expert personnel only.
No safety component in
accordance with the EU Machine
Directive
Proper use
pico+ultrasonic sensors are used for
non-contact detection of objects.
Installation
Mount the sensor at the installa-
tion site.
Connect a connection cable to the
M12 device plug.
Start-Up
Connect the power supply.
Carry out the sensor adjustment in
accordance with the diagram.
Fig. 1: Pin assignment with view onto sensor
plug and colour coding of the
microsonic connection cable
Factory Setting
Rising analogue characteristic
curve between the blind zone and
the operating range
Multifunctional input »Com« set
to »Teach-in«
1
3
colour
+U
B
-U
B
brown
blue
4
2
5
-
I|U
black
white
Com
grey
1
5
2
3
4
Synchronization
If the assembly distance falls below
the values shown in Fig. 2, the inter-
nal synchronization should be used.
For this purpose set the switched
outputs of all sensors in accordance
to the diagram »Sensor adjustment
with Teach-in procedure« at first.
Then set the multifunctional output
»Com« to »synchronization« (see
»Further settings«). Finally connect
pin 5 of the sensors plug of all sen-
sors.
Fig.2: Assembly distances, indicating syn-
chronization
Maintenance
microsonic sensors are maintenance-
free. In case of excess caked-on dirt
we recommend to clean the white
sensor surface.
Notes
The sensors of the pico+ family
have a blind zone. Within this
zone a distance measurement is
not possible.
The pico+ sensors are equipped
with an internal temperature com-
pensation. Due to the sensors self
heating, the temperature compen-
sation reaches its optimum work-
ing-point after approx. 20 minutes
of operation.
In the normal operating mode, an il-
luminated yellow LED signals the ob-
ject is within the adjusted window
limits.
If synchronization is activated the
Teach-in is disabled (see »Further
settings«).
The sensor can be reset to its fac-
tory setting (see »Further set-
tings«).
Optionally all Teach-in and addi-
tional sensor parameter settings
can be made using the LinkCon-
trol adapter (optional accessory)
and the LinkControl software for
windows© .
≥0,25 m
≥0.35 m
≥1,30 m
≥2.50 m
≥0.40 m
≥0.70 m
≥2.50 m
≥4.00 m
A
B
Ultrasonic Sensors
Set analogue output
Further settings