Led displays and the "factory default" button, Mechanical, Environmental – Measurement Computing E-PDISO16 User Manual
Page 26: Main connector, Led displays and the "factory default" button -3, Mechanical -3, Environmental -3, Main connector -3

E-PDISO16 User's Guide
Specifications
Ethernet and input filter "Factory Default" settings
Table 8. Factory default specifications
Default IP address
10.0.2.251
Default IP mask
255.255.255.252
Default Gateway 10.0.2.1
Default DHCP setting
Enabled
Default Filter setting
All Filters Off
LED displays and the "Factory Default" button
Table 9. LED and button configurations
POWER LED
6.0 V < V
ext
< 12.5 V
On
V
ext
<6.0 V
,
V
ext
> 12.5 V
Off (power fault)
TEST LED
Blinks when commanded to by software.
LINK LED
On when there is a valid Ethernet connection.
ACTIVITY
Blinks when an Ethernet packet is sent or received.
Factory default button
Returns the device to its factory default condition including resetting all Ethernet, filter
and relay conditions.
Mechanical
Table 10. Mechanical specifications
17.0" (L) x 4.8" (W) x 0.8" (H)
Card dimensions
431.8 mm (L) x 121 mm (W) x 20.3 mm (H)
17.2" (L) x 5.2” (H) x 1.6” (H)
Case dimensions
436.9 mm (L) x 132.1 mm (W) x 40.6 mm (H)
Environmental
Table 11. Environmental specifications
Operating temperature range
0 to 70 °C
Storage temperature range
-40 to 100 °C
Humidity
0 to 95% non-condensing
Main connector
Table 12. Main connector specifications
Connector type
Screw terminal
Wire gauge range
14-30 AWG
5-3