17 ~aa0 – Measurement Computing CB-COM-7013 User Manual
Page 34

34
CB-7013, CB-7033 User’s Manual
2.17 ~AA0
Description: Read Module Status
Syntax: ~AA0[CHK](cr)
~
Delimiter character
AA
Address of reading module (00 to FF)
0
Command for read module status
Response:
Valid Command:
!AASS[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax error or comm. error may get no response.
!
Delimiter for valid command.
?
Delimiter for invalid command.
AA
Address of response module (00 to FF).
SS
host watchdog time-out status, 00=status is clear ,
04=status is set. The status will store into EEPROM and
only may reset by the command ~AA1.
Example:
Command: ~010
Receive: !0100
Read address 01 module status, return 00.
Command: ~020
Receive: !0204
Read address 02 module status. A return of 04, means the
host watchdog time-out status is set; module is in safe mode.
Related Command:
Sec. 2.16
~**, Sec. 2.18 ~AA1, Sec. 2.19 ~AA2,
Sec. 2.20
~AA3EVV
Related Topic: Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog
Operation