3 #aa – Measurement Computing CB-COM-7013 User Manual
Page 20

20
CB-7013, CB-7033 User’s Manual
2.3 #AA
Description: Read Analog Input
Syntax: #AA[CHK](cr)
#
Delimiter character
AA
Address of reading module(00 to FF)
Response:
Valid Command:
>(Data)[CHK](cr)
Syntax error or communication error may get no
response.
>
Delimiter for valid command.
(Data)
Analog input value, reference Sec. 1.9 for its format
While using #AA command to CB-7033/33D, the data is
the combination for each channel respectively.
Example:
Command: #01
Receive: >+026.35
Read address 01, get data successfully.
Command: #02
Receive: >4C53
Read address 02, get data in HEX format successfully.
Command: #03
Receive: >-0000
Read address 03, get data underrange.
Command: #04
Receive: >+025.12+054.12+150.12
Read address 04, is I7033/I7033D, get 3 channel data.
Related Command:
Sec2.1
%AANNTTCCFF, Sec. 2.7 $AA2
Related Topics:
Sec. 1.9
Configuration Tables