beautypg.com

7 $aa2 – Measurement Computing CB-COM-7013 User Manual

Page 24

background image

24

CB-7013, CB-7033 User’s Manual

2.7 $AA2

Description: Read Configuration
Syntax: $AA2[CHK](cr)
$

Delimiter character

AA

Address of reading module (00 to FF)

2

Command for read configuration

Response:

Valid Command:

!AATTCCFF[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax error or communication error may get no re-
sponse.

!

Delimiter for valid command.

?

Delimiter for invalid command.

AA

Address of response module (00 to FF).

TT

Type code of module (reference Sec. 1.9).

CC

Baud rate code of module (reference Sec. 1.9).

FF

Data format of module (reference Sec. 1.9).

Example:
Command: $012

Receive: !01200600

Read address 01 configuration, return successful

Command: $022

Receive: !02230602

Read address 02 configuration, return successful.

Related Command:

Sec2.1

%AANNTTCCFF

Related Topics:

Sec. 1.9

Configuration Tables, Sec3.1 INIT* pin Operation.

This manual is related to the following products: