1 %aannttccff – Measurement Computing CB-COM-7013 User Manual
Page 17
17
CB-7013, CB-7033 User’s Manual
2.1 %AANNTTCCFF
Description: Set module configuration
Syntax: %AANNTTCCFF[CHK](cr)
%
A delimiter character.
AA
Address of setting module(00 to FF).
NN
New address for setting module(00 to FF).
TT
New type for setting module (Ref Sec. 1.9).
CC
New baud rate for setting module (Ref Sec. 1.9). It is
needed to short the INIT* to ground while change baud
rate. (Ref Sec. 3.1).
FF
New data format for setting module (Ref Sec. 1.9). It is
needed to short the INIT* to ground to change checksum
setting (Ref Sec. 3.1).
Response:
Valid Command:
!AA[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
!
Delimiter for valid command.
?
Delimiter for invalid command. While change baudrate
or checksum setting without short INIT* to ground, the
module will return invalid command.
AA
Address of response module(00 to FF)
Example:
Command: %0102200600
Receive: !02
Change address from 01 to 02, return successful.