DELTA MCS-1800 3U Power Shelf

Installation, Operations and

Maintenance Manual

2-4

Table 1 displays the system input specifications.

Table 1 System Input Specifications

Specification Value

Nominal range

175 ~ 275VAC

Operational range

90 ~ 275VAC Full Load
150V ~ 175Vac de-rating to 80% Load
90V ~ 150Vac de-rating to 50% Load

50℃ ~ 65℃ de-rating 1500W

Frequency 45

~

65Hz

Power Factor

>0.99 @ 220VAC, Full Load

THD

<5% @ 220VAC, Full Load

Efficiency

>90% @ 220VAC, Full Load

2.4.2 Output

Table 2 displays the system output specifications.

Table 2 System Output Specifications

Specification Value

DC Volts

38~60 VDC (-48V Version)
20~30 VDC (+24V Version)

Load regulation

<1%

Line regulation

<0.2%

Current Limit

110%

Current share

<5%

Noise:

Audio band
Wide band
Acoustic


<2mv
<10 mVrms
<55 dBA

2.4.3 Status/Alarm Indicators

The Power Shelf has the following status/alarm indicators:

Load Current
AC ON
Rectifier Fail Alarm (RFA)
Current Limit (CL)
Float/Equalize (FL/EQU)
Major Alarm (MAJ)
Minor Alarm (MIN)
High Voltage Alarm (HV)
High Voltage Shutdown (HVSD)
Low Voltage Alarm (LV)
Low Voltage Disconnect Open (LVDS OPEN)
Fuse Blown (FUSE ALM)
AC Fail (AC FAIL)