DELTA MCS-1800 3U Power Shelf

Installation, Operations and

Maintenance Manual

4-6

Settings Description

Comment

Function
Battery Max. Capacity

Default
Range

Parameter

Default
Range



- 74AH
- 1~2500

AH


- 4
- 1~20

Temperature Shut Down

Function
Default
Recovery


-

High Temperature Shutdown

- 149℉
- 122℉

Control:

Settings Description

Comment

Remote SMR On/Off

- Function

- Remote SMR on/off capability exists through the

CSU control.

- Description

- CSU automatically shuts down SMR in case of

DC high voltage.

- Users can manually shut down SMR from

Remote Management System.


SMR Shutdown
(1-3)

Floating / Equalize control

- Function

- SMR floating/equalize status can be set through

the CSU control.

- Description

- CSU automatically transfer SMR to floating

mode in case of mains recover after deep
discharge resulted from blackout/battery test

- Users can manually set SMR to floating or

equalize from CSU.








HVSD Recovery

- Function

- When system HVSD alarm recovery and system

voltage reduce to normal, this function is used to
reset the HVSD alarm