Delta MCS-1800 User Manual
Page 7
DELTA MCS-1800 3U Power Shelf
Installation, Operations and
Maintenance Manual
2-2
Environmental Data
System Environmental Data
Specification Value
Operating temperature
0℃ to +50℃
Storage temperature
-40℃ to +70℃
Humidity
0% to 95% RH
Altitude
-300 ft. to 10,000 ft.
Weight
Approximately 48 lbs.
EMI/FRI
FCC Part 15, Class B and CISPR 22, Class B
Lightning/surge ANSI/IEEE
C62.41-1, and IEC 1000-4-5
Seismic
Bellcore GR-63-CORE, Zone 4
Safety
CUL and UL Listed and Marked
2.3.2 +24V Standard Power Shelf Configuration(MODUL NAME: ES24/200-JAAxx)
(1) AC Input:
175VAC ~ 275VAC, 48Amps. Max
(2) System Capacity:
200Amps. Max.
(3) Rectifier:
+24V/50A×1~4
(4) Control and Supervisory
Figure 1 shows a front view of shelf.
Environmental Data
System Environmental Data
Specification Value
Operating temperature
0℃ to +50℃
Storage temperature
-40℃ to +70℃
Humidity
0% to 95% RH
Altitude
-300 ft. to 10,000 ft.
Weight
Approximately 48 lbs.
Lightning/surge ANSI/IEEE
C62.41-1, and IEC 1000-4-5
Seismic
Bellcore GR-63-CORE, Zone 4
Safety
CUL and UL Listed and Marked
2.3.3 -48V System with Power Distribution and Rectifiers(MODUL NAME: ES48/90-JBAxx)
(1) AC Input:
175VAC ~ 275VAC, 36Amps. Max
(2) System Capacity:
90Amps. Max.
(3) Rectifier:
-48V/30A×1~3
(4) Control and Supervisory
(5) Load Distribution:
30A Breaker×5 @ Single Pole
(6) Low Voltage Disconnect Switch: 100A×1 @ Single Pole at Battery Side
(7) Battery Breaker:
100A×1