beautypg.com

Delta MCS-1800 User Manual

Page 7

background image

DELTA MCS-1800 3U Power Shelf

Installation, Operations and

Maintenance Manual

2-2

Environmental Data

System Environmental Data

Specification Value

Operating temperature

0℃ to +50℃

Storage temperature

-40℃ to +70℃

Humidity

0% to 95% RH

Altitude

-300 ft. to 10,000 ft.

Weight

Approximately 48 lbs.

EMI/FRI

FCC Part 15, Class B and CISPR 22, Class B

Lightning/surge ANSI/IEEE

C62.41-1, and IEC 1000-4-5

Seismic

Bellcore GR-63-CORE, Zone 4

Safety

CUL and UL Listed and Marked

2.3.2 +24V Standard Power Shelf Configuration(MODUL NAME: ES24/200-JAAxx)

(1) AC Input:

175VAC ~ 275VAC, 48Amps. Max

(2) System Capacity:

200Amps. Max.

(3) Rectifier:

+24V/50A×1~4

(4) Control and Supervisory

Figure 1 shows a front view of shelf.

Environmental Data

System Environmental Data

Specification Value

Operating temperature

0℃ to +50℃

Storage temperature

-40℃ to +70℃

Humidity

0% to 95% RH

Altitude

-300 ft. to 10,000 ft.

Weight

Approximately 48 lbs.

Lightning/surge ANSI/IEEE

C62.41-1, and IEC 1000-4-5

Seismic

Bellcore GR-63-CORE, Zone 4

Safety

CUL and UL Listed and Marked

2.3.3 -48V System with Power Distribution and Rectifiers(MODUL NAME: ES48/90-JBAxx)

(1) AC Input:

175VAC ~ 275VAC, 36Amps. Max

(2) System Capacity:

90Amps. Max.

(3) Rectifier:

-48V/30A×1~3

(4) Control and Supervisory

(5) Load Distribution:

30A Breaker×5 @ Single Pole

(6) Low Voltage Disconnect Switch: 100A×1 @ Single Pole at Battery Side

(7) Battery Breaker:

100A×1

(8) AC Breaker